background image

P/N 3100010-

EN • REV 09 • ISS 14JAN15

 

 

9

 / 10 

Table 5: PLC compatibility: PLC output to meet following product input parameters 
Model number 

Operating voltage 

Max. off state leakage 

current 

Continuous on current 

Surge (inrush/duration) 

5540M

-

24AQ

 

24 VDC only

 

2 mA

 

740 mA

 

8 A / 4 mS

 

5540M

-

24N5

 

120 VAC 50/60 Hz

 

2 mA

 

360 mA

 

2.82 A / 4 mS

 

5540M

-

24Y6

 

120 VAC 50/60 Hz

 

2 mA

 

320 mA

 

2.82 A / 4 mS

 

5540M

-

120N5

 

120 VAC 50/60 Hz

 

5 mA

 

380 mA

 

2.82 A / 4 mS

 

5540M

-

120Y6

 

120 VAC 50/60 Hz

 

5 mA

 

310 mA

 

2.82 A / 4 mS

 

5540MV

-

24N5

 

120 VAC 50/60 Hz

 

2 mA

 

360 mA

 

2.82 A / 4 mS

 

5540MV

-

24Y6

 

120 VAC 50/60 Hz

 

2 mA

 

320 mA

 

2.82 A / 4 mS

 

Input board circuit

 

24

 

VDC

 

2 mA

 

6 mA

 

— 

Input board circuit

 

120 VAC 50/60 Hz

 

5 mA

 

13 mA

 

— 

Note: Refer to Figure

 

9

 

and Figure

 

12

 

for wiring.

 

Table 6: Tone programming 
Tone 

SW4-6  SW4-5  SW4-4  SW4-3  SW4-2  SW4-1  Description 

Hex 

No Tone

 

OFF 

OFF 

OFF 

OFF 

OFF 

OFF 

No tone

 

00 

Ding

-

Dong

 

OFF 

OFF 

OFF 

OFF 

OFF 

ON 

Percussive pairs of 700 and 570 Hz tones, each 

damped to 0

 

01 

Warble

 

OFF 

OFF 

OFF 

OFF 

ON 

OFF 

575 and 770 Hz alternately, 87 ms each

 

02

 

Siren

 

OFF 

OFF 

OFF 

OFF 

ON 

ON 

600 to 1250 Hz up and down sweep in 8 s and 

repeat

 

03 

Stutter

 

OFF 

OFF 

OFF 

ON 

OFF 

OFF 

Percussive 470 Hz, 83 ms on, 109 ms off

 

04

 

Slow Whoop

 

OFF 

OFF 

OFF 

ON 

OFF 

ON 

600 to 1250 Hz upward sweep in 4 s and repeat

 

05

 

Beep

 

OFF 

OFF 

OFF 

ON 

ON 

OFF 

470 Hz, 0.55 s on, 0.55 s off

 

06 

Chime 1

 

OFF 

OFF 

OFF 

ON 

ON 

ON 

700 Hz percussive repeat at 1 Hz

 

07

 

Fast Whoop

 

OFF 

OFF 

ON 

OFF 

OFF 

OFF 

600 to 1250 Hz upward in 1 s and repeat

 

08 

Hi/Lo

 

OFF 

OFF 

ON 

OFF 

OFF 

ON 

780 to 600 Hz alternately, 0.52 s each

 

09

 

Rapid Siren

 

OFF 

OFF 

ON 

OFF 

ON 

OFF 

600 to 1250 Hz up and down sweep in 0.25 s and 

repeat

 

0A

 

Yeow

 

OFF 

OFF 

ON 

OFF 

ON 

ON 

1250 to 600 Hz downward sweep in 1.6 s and 

repeat

 

0B

 

Horn

 

OFF 

OFF 

ON 

ON 

OFF 

OFF 

470 Hz continuous

 

0C

 

Air Horn

 

OFF 

OFF 

ON 

ON 

OFF 

ON 

370 Hz continuous

 

0D

 

Dual Tone

 

OFF 

OFF 

ON 

ON 

ON 

OFF 

470 to 500 Hz, 0.4 to 0.5 s cycle

 

0E 

Chime 2

 

OFF 

OFF 

ON 

ON 

ON 

ON 

575 Hz percussive repeat at 1 Hz

 

0F 

Westminster

 

OFF 

ON 

OFF 

OFF 

OFF 

OFF 

Two measures, 411 Hz, 520 Hz, 407 Hz, 312 Hz

 

10 

Three Blind Mice

 

OFF 

ON 

OFF 

OFF 

OFF 

ON 

Four measures, 787 Hz, 714 Hz, 625 Hz, 952 Hz, 

 

333 Hz

 

11 

Phasor

 

OFF 

ON 

OFF 

OFF 

ON 

OFF 

416 to 625 Hz up and down sweep in 13 ms and 

repeat

 

12

 

Telephone

 

OFF 

ON 

OFF 

OFF 

ON 

ON 

570 and 770 Hz alternately, 50 ms each for 1.2

 

s, 

1.5

 

s delay and repeat

 

13 

Staircase

 

OFF 

ON 

OFF 

ON 

OFF 

OFF 

440 to 2000 Hz up and down steps, 750 ms delay 

and repeat

 

14

 

3 Tone Alert

 

OFF 

ON 

OFF 

ON 

OFF 

ON 

463 Hz, 641 Hz, and 896 Hz, 200 ms each, 1 s 

delay and repeat

 

15

 

RESERVED

 

OFF 

ON 

OFF 

ON 

ON 

OFF 

RESERVED

 

16 

RESERVED

 

OFF 

ON 

OFF 

ON 

ON 

ON 

RESERVED

 

17

 

RESERVED

 

OFF 

ON 

ON 

OFF 

OFF 

OFF 

RESERVED

 

18 

RESERVED

 

OFF 

ON 

ON 

OFF 

OFF 

ON 

RESERVED

 

19

 

RESERVED

 

OFF 

ON 

ON 

OFF 

ON 

OFF 

RESERVED

 

1A

 

NFPA Whoop

 

OFF 

ON 

ON 

OFF 

ON 

ON 

Three 422 to 775 Hz upward sweeps, 850 ms each, 

1 s delay and repeat

 

1B

 

3 Pulse Horn

OFF 

ON 

ON 

ON 

OFF 

OFF 

470 Hz, 3 0.5 s pulses separated by 0.5 s followed 

by 1.5 s delay and repeat

 

1C

 

3 Pulse Air Horn

OFF 

ON 

ON 

ON 

OFF 

ON 

370 Hz, 3 0.5 s pulses separated by 0.5 s followed 

by 1.5

 

s

 

delay and repeat

 

1D

 

3 Pulse Dual Tone

OFF 

ON 

ON 

ON 

ON 

OFF 

450 to 500 Hz, 0.4 to 0.5 s cycle, three

 

0.5

 

s pulses 

separated by 0.5 s followed by 1.5 s delay and 

repeat

 

1E 

3 Pulse Chime 2

OFF 

ON 

ON 

ON 

ON 

ON 

575 Hz, 3 0.5 s pulses separated by 0.5 s followed 

by 1.5 s delay and repeat

 

1F 

European Police

 

ON 

OFF 

OFF 

OFF 

OFF 

OFF 

969 Hz and 800 Hz alternately 0.250 s each

 

20

 

Содержание Adaptatone 5532M

Страница 1: ...ue to long wire runs needs to be accounted for in sizing wire Consult Applications Engineering for details For Model numbers ending in AQ 24 VAC power must be transformer isolated from mains or line p...

Страница 2: ...lead of the 5540 tone generator Up to 2500 speaker amplifiers can be so connected in parallel to a single tone generator c For the tone generator select the appropriate method for wiring to the input...

Страница 3: ...s necessary Set the main volume using the potentiometer on the main board Figure 14 through Figure 16 and then set the voice volume using the potentiometer on the voice module board Figure 16 Maintena...

Страница 4: ...1 Power and earth ground leads black and white or black for power yellow striped green for earth ground 2 Plastic cable ties provided Use to separate power leads from signal and tone initiating leads...

Страница 5: ...oard Figure 11 Wiring multiple dry contacts to 120 V tone generator input board 1 On the input board 2 Neutral 3 120 VAC 4 Line Figure 12 Connecting from a PLC to 120 V tone generator input board 1 PL...

Страница 6: ...volume adjustment Figure 15 5540M Series PC board locations 1 Input board 2 Programming switches other side 3 Main board 4 Direction of increasing volume 5 Potentiometer for volume adjustment 6 Proce...

Страница 7: ...Speaker amplifier 5532B Y6 or 5532BHV Y6 5 Potentiometer for volume adjustment 6 Increase 7 Decrease 8 Battery backup 9 Tone in 10 Speaker amplifier 5532B AQ or 5532BHV AQ 11 24 to 36 VDC or 24 VAC 12...

Страница 8: ...A Speaker Amplifier at standard volume 5532M AQ 24 VDC 24 VAC 50 60 Hz 0 10 A 0 10 A 0 74 A 1 3 A 5532M N5 120 VAC 50 60 Hz 0 10 A 0 36 A Model number Voltage Standby current Tone on current 5532M Y6...

Страница 9: ...sweep in 0 25 s and repeat 0A Yeow OFF OFF ON OFF ON ON 1250 to 600 Hz downward sweep in 1 6 s and repeat 0B Horn OFF OFF ON ON OFF OFF 470 Hz continuous 0C Air Horn OFF OFF ON ON OFF ON 370 Hz conti...

Страница 10: ...or 0 1009 s 235 Hz for 0 050 s 2F Multi tone ON ON OFF OFF OFF OFF 376 357 352 382 355 375 384 375 and 364 Hz alternately on for 0 050 s 30 Attention ON ON OFF OFF OFF ON 2232 4545 3704 2777 4347 3704...

Отзывы: