MMU-16LE
SmartMonitor
Operations Manual
Eberle Design Inc.
Page 26
4.1.5 MANUAL RESET (MR) EVENT LOG
The monitor was reset from a fault by the front panel Reset button or External Reset input
or non-latched fault clear.
4.1.6 CONFIGURATION (CF) EVENT LOG
Program Card Matrix: the permissive programming for each channel.
MYCD Jumpers: the Minimum Yellow Clearance Disable programming for each channel.
Enhanced Programming Parameters: Unit, Field Check, Red Fail, Dual Indication, and
MYRCD programming
NEMA Inputs: 24V Inhibit, Type Select, Port 1 Disable.
Program Card: Minimum Flash Timing, 24V & CVM Latch Enables.
Configuration Check Value
4.1.7 SIGNAL SEQUENCE EVENT LOG
: the value of the 16 bit Check Value for the reported
configuration.
The Signal Sequence event log graphically displays all signal states and Red Enable state
for up 30 seconds prior to the MMU-16LE
SmartMonitor
®
fault trigger for the most recent
five (5) Previous Fault (PF) events.
4.2 CONFIGURATION PROGRAMMING
The ECcom software provides a method for displaying and setting the configuration
programming of the MMU-16LE. Programming functions on the Nema Program Card are
read only by the ECcom software. All other Nema enhanced functions can be set directly
by the software.
ECcom can also save the configuration setup of the MMU-16LE
SmartMonitor
®
to a disk file
or retrieve a configuration from a disk file.
4.2.1 ECCOM CONFIGURATION SET-UP WIZARD
The Set-up Wizard in ECcom can be used to automatically generate all the enhanced
monitor programming data for the MMU-16LE
SmartMonitor
®
in most cases without the
need for understanding complex and confusing monitor terminology. It works in the same
fashion as the built-in Setup Wizard (see Section 6.3.14), and configures the monitor
enhanced-feature programming using a simple series of intersection related questions. The
resulting output from the ECcom Setup Wizard can then be downloaded to the target MMU-
16LE
SmartMonitor
®
unit.
4.3 ETHERNET LAN PORT
The optional Ethernet port must be configured with specific network parameters such as an
IP address and Subnet Mask. The network port parameters are set or changed using the
EDI
ECcom
®
Signal Monitor Communications software. See the "
EDI ECcom
®
Software
Operations Manual
" ETHERNET LAN SETTINGS Section 3.2.1.2 for details.