PVCT COLINEAR TRANSITION VENT KIT
Available from Empire Comfort Systems, Inc.
Flat Roof or Chimney Application
1. Attach plate to chimney chase or flat roof with four (4) screws. Use outdoor sealant to seal transition plate to the roof or chimney
chase.
2. Check local codes to determine air intake height from roof. The minimum height for this application is 12”.
3. Cut 1 1/2” PVC pipe to correct height. Attach pipe, PTrap, and exhaust cap to plate. Glue all joints with PVC cement.
AIR INTAKE
PTRAP OR 2 90° ELBOWS
SUPPLIED BY INSTALLER
TRANSITION PLATE
PVC CEMENT
PVC CEMENT
OUTDOOR SEALER REQUIRED
OPTIONAL
CAP
MODEL PVVTC
ORDER SEPARATE
EXHAUST
3” MIN.
HEIGHT (MIN. 12”)
Horizontal Application
1. Attach plate to outside wall with four (4) screws. Use outdoor sealant to seal transition plate to the wall.
2. Cut 1 1/2” PVC pipe to correct length. The minimum length for this application is 9” for the exhaust and 6” for the air intake. Glue
all joints with PVC cement.
Colinear Transition Plate
AIR INTAKE
PTRAP OR 2 90° ELBOWS
SUPPLIED BY INSTALLER
TRANSITION PLATE
PVC CEMENT
PVC CEMENT
OUTDOOR SEALER REQUIRED
3” MIN.
HEIGHT (MIN. 12”)
EXHAUST
PTRAP OR 2 90° ELBOWS
SUPPLIED BY INSTALLER
Note:
Must maintain a minimum 3” between
exhaust outlet and air intake.
Note:
Exhaust must be a minimum of 3” above air intake inlet.