SPECIFICATIONS & SYSTEM PERFORMANCE
CHILLED WATER 2-PIPE CASSETTE COOLING CAPACITIES
COOLING CAPACITY
CHILLED WATER ENTERING / LEAVING TEMPERATURE ºF (no glycol)
Air Flow
MODEL
Entering
Dry Bulb Air
Temperature
(ºF) at 50%
RH
40/50° F
45/55° F
Total
Capacity
Sensible
Capacity
Flow
Rate
Pressure
Drop
Total
Capacity
Sensible
Capacity Flow Rate
Pressure
Drop
Btuh
Btuh
GPM
FT. Water
Btuh
Btuh
GPM
FT. Water
CFM
08
72
7,700
7,300
1.5
3.3
5,900
5,900
1.2
2.0
360
75
9,100
8,000
1.8
4.5
7,200
6,900
1.4
2.9
80
12,900
9,400
2.6
8.6
9,600
8,100
1.9
4.9
12
72
10,500
8,900
2.1
1.9
7,400
7,200
1.5
0.9
360
75
12,700
9,900
2.5
2.9
9,300
8,400
1.9
1.5
80
17,700
11,700
3.5
5.4
13,500
10,000
2.7
3.2
18
72
11,800
11,800
2.3
0.6
9,000
9,000
1.8
0.4
650
75
15,900
14,300
3.2
1.0
10,700
10,700
2.1
0.5
80
24,000
17,700
4.8
2.5
18,000
15,100
3.6
1.3
20
72
12,300
12,300
2.4
0.6
9,300
9,300
1.9
0.4
700
75
17,200
15,400
3.4
1.2
11,200
11,200
2.2
0.5
80
27,200
19,400
5.4
3.2
19,400
16,300
3.9
1.6
33
72
26,700
22,900
5.3
2.7
19,200
18,800
3.8
1.3
950
75
33,300
25,800
6.6
4.4
23,900
21,700
4.8
2.2
80
50,300
32,400
10.0
9.4
36,800
26,700
7.3
5.2
36
72
30,500
26,300
6.1
3.7
21,900
21,500
4.4
1.8
1100
75
39,700
30,400
7.9
6.1
27,300
24,900
5.5
2.9
80
58,400
37,600
11.6
12.5
42,500
31,200
8.7
7.2
50 Hz No Derate - 115v Transformer no Derate
2-PIPE CASSETTE
Model
Air Flow
High
Speed
Low
Speed
CFM
CFM
CAW08
360
300
CAW12
360
300
CAW18
650
550
CAW20
700
600
CAW33
950
750
CAW36
1100
900
CAW HOT WATER 4-PIPE CASSETTE CAPACITIES
HOT WATER ENTERING TEMPERATURE 180°F
Model
Room
Conditions
Heating
Capacity
Btuh
Water
Flow GPM
Leaving
Water
Temperature
P.D. Ft.
H
2
O
CAW08
70 °F DB
13,300
1.4
160 °F
2.8
50% RH
10,000
0.5
*140 °F
0.5
CAW12
70 °F DB
17,000
1.8
160 °F
1.6
50% RH
13,500
0.7
140 °F
0.5
CAW18
70 °F DB
29,800
3.2
160 °F
2.8
50% RH
22,500
1.2
140 °F
0.2
CAW20
70 °F DB
30,800
3.5
160 °F
2.8
50% RH
23,200
1.2
140 °F
0.2
CAW33
70 °F DB
49,500
5.4
160 °F
8.3
50% RH
37,800
2.1
140 °F
2.3
CAW36
70 °F DB
53,900
5.6
160 °F
9.2
50% RH
40,600
2.2
140 °F
2.3
* 140°F Leaving water temperature data is in accordance with ANSI/AHRI
Standard 440-2008