24
PN 20009722 REV E, [02/11/2015]
CAW INFRARED CONTROL SYSTEM - OVERVIEW
DIP Switch
Setting
Operation
Factory
Setting
#1
Test mode
YES
Enables Test Mode
. Timers are shortened, quick
operational testing.
• Anti-short-cycle time reduces from 3 minutes to 45
seconds.
• Minimum on-time reduces from 2 minutes to 30
seconds.
• Post-purge time reduces from 60 to 15 seconds.
• Stagger start time reduces from 30 to 7.5 seconds.
NO
NO
D
isables Test Mode.
#2
Louver oscillation
(for wall mounted
thermostat mode only)
On
If DIP Switch #4 is YES,
enables louver oscillation
during
operation.
OFF
Off
If DIP Switch #4 is YES,
disables louver oscillation
during
operation.
#3
Fan speed setting
(for wall mounted
thermostat mode only)
HIGH
While DIP Switch #4 is YES, selects fan speed
HIGH
.
HIGH
LOW
While DIP Switch #4 is YES, selects fan speed
LOW
.
#4
Select infrared handheld
controller or wall
mounted thermostat
control
YES
Disables infrared hand controller
and enables wall
mounted thermostat operation. Enables dip switches #3 and
#2.
Clean filter time automatically defaults to 1000 hours.
YES
NO
Enables infrared hand controller
and disables wall
mounted thermostat operation.
Table 3 - CAW Microprocessor Controller — Dip Switch Settings