background image

Johnson Controls Ducted Systems

5724452-UIM-A-0619

STANDARD ECM
MODULAR MULTI-POSITION 
AIR HANDLERS

MODELS: ME SERIES - 208/230 V - 1 PHASE

INSTALLATION MANUAL

ISO 9001

Certified Quality

Management System

LIST OF SECTIONS

GENERAL  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
SAFETY  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
UNIT INSTALLATION  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
DUCT WORK AND CONNECTIONS   . . . . . . . . . . . . . . . . . . . . . . . . . 5
ELECTRIC HEATER INSTALLATION   . . . . . . . . . . . . . . . . . . . . . . . . 6
LINE POWER CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
LOW VOLTAGE CONTROL CONNECTIONS   . . . . . . . . . . . . . . . . . . 7
BLOWER SPEED CONNECTIONS   . . . . . . . . . . . . . . . . . . . . . . . . . . 7

UNIT DATA   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  8
MAINTENANCE  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  14
AIR SYSTEM ADJUSTMENT   . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  14
TYPICAL THERMOSTAT CONNECTIONS . . . . . . . . . . . . . . . . . . .  14
WIRING DIAGRAM   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  15
TYPICAL THERMOSTAT CONNECTIONS . . . . . . . . . . . . . . . . . . .  17
START UP SHEET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  19

LIST OF FIGURES

Return Air Duct Attachment  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Typical Installation  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Coil and Air Handler Attachment Details  . . . . . . . . . . . . . . . . . . . . . . . 3
Gasket Location  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Dimensions and Duct Connection Dimensions   . . . . . . . . . . . . . . . . . . 4
Typical Horizontal Installation   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Duct Attachment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Duct Work Transition  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Line Power Connections   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

Blower Speed Connections   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  7
Duct Static Measurements  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  14
Typical Thermostat Wiring Diagram - Single Stage 
Outdoor - ECM  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  14
Wiring Diagram - Standard ECM - Single Phase Heat Kits   . . . . . . .  15
Wiring Diagram - Three Phase Heat Kits  . . . . . . . . . . . . . . . . . . . . .  16
Typical Thermostat Wiring Diagram - 2 Stage Heat Pump with
ECM Blower Motor  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  17

LIST OF TABLES

Dimensions   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Physical and Electrical Data - Cooling Only . . . . . . . . . . . . . . . . . . . . . 8
Electrical Data - Cooling Only   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Minimum Fan Speed - Electrical Heat with Heat Pump  . . . . . . . . . . . . 8
Default Blower Speeds for FER Compliance - Electrical Heat Only   . . 9
KW and MBH Conversions - For Total Power Input Requirement  . . . . 9

Electric Heat Performance Data: 208/230-1-60 and 208/230-3-60   . .  9
Electrical Data for Single Source Power Supply: 208/230-1-60  . . . .  10
Electrical Data for Multi-source Power Supply: 208/230-1-60   . . . . .  11
Electrical Data for Single Source Power Supply: 208/230-3-60  . . . .  11
Electrical Data for Multi-source Power Supply: 208/230-3-60   . . . . .  12
Airflow Data (CFM)  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  12

SECTION I: GENERAL

The ME modular air handler series provides the flexibility for installation
in any position. This unit may be used for upflow, downflow, horizontal
right, or horizontal left applications.
These units may be located in a closet, utility room, attic, crawl space,
or basement. These versatile models may be used for cooling or heat
pump operation with or without electric heat or indoor coil.
Top or side power and control wiring, color coded leads for control
wiring, and electric heaters all combine to make the installation easy
and minimize installation cost.
Electric heat kits are available as field installed accessories. Single
phase kits are available from 2.5 kW to 25 kW. 208-230 volt three
phase kits are available from 10 kW to 25 kW.

SECTION II: SAFETY

This is a safety alert symbol. When you see this symbol on
labels or in manuals, be alert to the potential for personal
injury.

Understand and pay particular attention to the signal words 

DANGER

,

WARNING

, or 

CAUTION

DANGER 

indicates an 

imminently

 hazardous situation, which, if not

avoided, 

will result in death or serious injury

.

WARNING 

indicates a 

potentially

 hazardous situation, which, if not

avoided, 

could result in death or serious injury

.

CAUTION 

indicates a potentially hazardous situation, which, if not

avoided 

may  result  in  minor  or  moderate  injury.

 It is also used to

alert against unsafe practices and hazards involving only property
damage.

 WARNING

FIRE OR ELECTRICAL HAZARD

Failure to follow the safety warnings exactly could result in serious
injury, death or property damage. A fire or electrical hazard may result
causing property damage, personal injury or loss of life.

 WARNING

The air handler area must not be used as a broom closet or for any other
storage purposes, as a fire hazard may be created. Never store items
such as the following on, near or in contact with the furnace.

1. Spray or aerosol cans, rags, brooms, dust mops, vacuum clean-

ers or other cleaning tools.

2. Soap powders, bleaches, waxes or other Cleaning compounds;

plastic items or containers; gasoline, kerosene, cigarette lighter
fluid, dry cleaning fluids or other volatile fluid.

3. Paint thinners and other painting compounds.
4. Paper bags, boxes or other paper products

Never operate the air handler with the blower door removed. To do so
could result in serious personal injury and/or equipment damage.

!

!

Summary of Contents for ME Series

Page 1: ...ns These units may be located in a closet utility room attic crawl space or basement These versatile models may be used for cooling or heat pump operation with or without electric heat or indoor coil Top or side power and control wiring color coded leads for control wiring and electric heaters all combine to make the installation easy and minimize installation cost Electric heat kits are available...

Page 2: ... for inspection by the carrier s agent must be made in writing Also before installation the unit must be checked for screws or bolts that may have loosened in transit There are no shipping or spacer brackets which need to be removed It must be verified that all accessories such as heat kits and coils are available Installation of these accessories or field conversion of the unit must be done befor...

Page 3: ...casing may occur On these installations unit duct connections and other openings must be properly sealed and a wrap of 2 fiberglass insulation with vinyl vapor barrier must be used AIR HANDLER CONFIGURATION These air handler units are supplied ready to be installed in an upflow downflow horizontal right or horizontal left position Refer to Figure 2 The unit requires no conversion procedures AIR HA...

Page 4: ...M INLET DIMENSIONS C D 12 3 16 19 1 8 B 20 1 2 21 1 2 TABLE 1 Dimensions ME MODELS Dimensions1 Wiring Knockout Dimensions1 A B C D E F Height Width Bottom Opening Top Opening Power Control ME08B 21 1 2 17 1 2 16 1 2 16 1 2 7 8 1 2 1 3 8 1 1 23 32 1 1 4 7 8 1 2 ME12B 21 1 2 17 1 2 16 1 2 16 1 2 ME12C 22 1 2 21 20 20 ME14D 22 1 2 24 1 2 23 1 2 23 1 2 ME16C 22 1 2 21 20 20 ME20D 22 1 2 24 1 2 23 1 2 ...

Page 5: ...t be designed in accordance with the Air Conditioning Contractors of America ACCA Manual D HORIZONTAL SUSPENSION For suspension of these units in horizontal applications it is recom mended to use angle steel support brackets with threaded rods sup porting the units from the bottom at the locations shown in Figure 6 DUCT FLANGES Three duct flanges are provided to assist in positioning and attaching...

Page 6: ...ired for Horizontal right hand airflow applica tion only Follow instructions with heater for modification SECTION VI LINE POWER CONNECTIONS Power may be brought into the unit through the supply air end of the unit top left when unit is vertical or the left side panel Use the hole appropriate to the unit s orientation in each installation to bring conduit from the disconnect The power lead conduit ...

Page 7: ...eat kit connected to tap 5 for the heating speed and the Yellow cooling heat pump lead connected to tap 4 for the cooling heat pump heating speed Move the electric heat kit wire for the heating speed from tap 5 to the appropriate speed tap according to Table 4 If electric heat requires speed tap 5 the highest speed tap available for cooling heat pump heating is tap 4 The circulating blower Green t...

Page 8: ...de or in Canada the Canadian Electrical Code and local codes to determine correct wire sizing TABLE 4 Minimum Fan Speed Electrical Heat with Heat Pump Heat Kit Models1 2 3 Nom kW 240 V Air Handler Models ME08B ME12B ME12C ME14D ME16C ME20D 6HK 0 1 6500206 2 4 kW Medium Low 2 Medium Low 2 Medium Low 2 Medium Low 2 Medium Low 2 Medium Low 2 6HK 0 1 6500506 4 8 kW Medium 3 Medium Low 2 Medium 3 Mediu...

Page 9: ... following table DISTRIBUTION POWER NOMINAL VOLTAGE CONVERSION FACTOR 208 V 240 V 0 75 220 V 240 V 0 84 230 V 240 V 0 92 TABLE 7 Electric Heat Performance Data 208 230 1 60 and 208 230 3 60 Heater Models1 2 3 Nominal kW 240 V Total Heat4 kW Staging kW MBH W1 Only W1 W2 208 V 230 V 208 V 230 V 208 V 230 V 208 V 230 V 1PH 6HK 0 1 6500206 2 4 1 8 2 2 6 2 7 5 1 8 2 2 1 8 2 2 6HK 0 1 6500506 4 8 3 6 4 ...

Page 10: ... 7 76 5 70 80 6HK 1 2 6501806 72 82 9 91 2 90 100 6HK 1 2 6502006 80 91 3 100 4 100 110 ME12C 6HK 0 1 6500206 10 15 6 16 7 20 20 6HK 0 1 6500506 20 26 4 28 7 30 30 6HK 0 1 6500806 32 39 6 43 3 40 45 6HK 0 1 6501006 40 48 0 52 6 50 60 6HK 1 2 6501306 52 61 2 67 3 70 70 6HK 1 2 6501506 60 69 7 76 5 70 80 6HK 1 2 6501806 72 82 9 91 2 90 100 6HK 1 2 6502006 80 91 3 100 4 100 110 ME14D 6HK 0 1 6500206 ...

Page 11: ...vice must be HACR type circuit breaker or time delay fuse Refer to the latest edition of the National Electrical Code or in Canada the Canadian Electrical Code and local codes to determine correct wire sizing TABLE 10 Electrical Data for Single Source Power Supply 208 230 3 60 Air Handler Models Heater Models1 Heater Amps 240 V Field Wiring Min Circuit Ampacity MOP 2 208 V 230 V 208 V 230 V ME08B ...

Page 12: ... High 5 923 892 862 833 797 743 688 Medium High 4 846 816 786 750 710 638 599 Medium 3 631 605 575 512 442 370 282 Medium Low 2 570 530 460 402 328 232 186 Low 1 477 448 372 292 203 157 24 CM30B High 5 937 905 877 841 798 748 704 Medium High 4 846 808 778 733 667 636 572 Medium 3 638 609 556 495 463 399 336 Medium Low 2 560 484 469 408 321 265 201 Low 1 481 448 390 328 252 166 92 ME12B CM18B High ...

Page 13: ...124 1060 1008 954 889 827 755 ME20D CM36D High 5 2061 2021 1979 1938 1904 1865 1829 Medium High 4 1998 1949 1914 1879 1835 1797 1756 Medium 3 1769 1711 1677 1643 1603 1570 1530 Medium Low 2 1557 1508 1469 1439 1398 1355 1323 Low 1 1340 1291 1252 1216 1170 1132 1058 CM42D High 5 2032 1996 1959 1913 1890 1849 1820 Medium High 4 1974 1938 1892 1855 1824 1785 1754 Medium 3 1752 1706 1680 1633 1591 154...

Page 14: ...s run the fan only to assure a dry coil Drill 2 holes one 12 away from the air handler in the supply air duct and on 12 away from the air handler in the return air duct before any elbows in the duct work Insert the pressure tips and read the pressure drop from the manometer See Table 12 to determine the airflow and make the necessary adjustments to keep the CFM within the airflow limitations of th...

Page 15: ...AGE FIELD WIRING CONNECTIONS LEGEND LS LIMIT SWITCH SEQ SEQUENCER HE HEATING ELEMENT FL FUSIBLE LINK H SEQUENCER HEATER RLY RELAY AIR HANDLER WITH NO HEAT KIT WIRING DIAGRAM 5724441 UWD A 0219 1 2 3 4 5 6 1 2 3 4 5 6 L2 L1 HE2 LS FL RLY 2 RLY 1 RED WHT EQUIPMENT GROUND YEL BLK BLU YEL WHT BLU PRP BLU BLU HE1 LS FL WHT HEATER KITS 6HK 6500806 6HK 6501006 1 2 3 4 5 6 24V 240V COM 208V 1 2 3 4 5 6 1 ...

Page 16: ...UE BLUE BLUE BLUE YELLOW YELLOW BLACK BLACK YELLOW YELLOW BLACK BLACK RED WHITE BLACK BLUE BLACK BLUE YELLOW BLACK YELLOW YELLOW BLUE BLACK BLUE BLACK YELLOW RLY 1 RLY 2 RLY 3 RLY 6 RLY 5 RLY 4 HE2 FL HE3 FL HE6 FL HE1 FL HE4 FL HE5 FL 5 4 3 2 6 1 WHITE BLUE PURPLE RED WHITE BLACK GND LS LS LS LS LS LS WHITE WHITE BLUE BLUE BLUE WHITE BROWN BROWN BLUE BLUE BROWN BLUE BROWN BLUE BLACK BLUE YELLOW B...

Page 17: ... HE1 HE2 LS LS HE3 LS FL FL FL SEQ2 SEQ1 RED WHT EQUIPMENT GROUND BLK RED YEL BLK RED BLK BRN WHT BLU PRP BLU YEL BLU 1 2 3 4 5 6 RLY BLU BLU BLU YEL BLU YEL BRN 3 1 5 4 H H 3 1 5 4 H H Y2 OUT W1 OUT W2 OUT C R Y1 Y2 W O C R Y1 Y2 W E O G DEFROST CONTROL BOARD 2 STAGE HEAT PUMP 3 STAGE HEAT 2 STAGE COOL ROOM TERMMOSTAT NOTICE WIRING FOR BLOWER MOTOR MAY REQUIRE FIELD ADJUSTMENT DEPENDING ON MATCHU...

Page 18: ...5724452 UIM A 0619 18 Johnson Controls Ducted Systems NOTES ...

Page 19: ...dry bulb temperature Return air dry bulb temperature Temperature drop 1 2 3 4 5 Low Medium Low Medium Medium High High A B C D Outside air dry bulb temperature Return air wet bulb temperature Supply air wet bulb temperature Return static inches of water column Electrical Connections Inspection Complete all that apply Continued on next Page ECM X 13 PSC A B C D Low voltage value between R and C at ...

Page 20: ...ting and correcting any problems Operate the unit through cooling cycles from the thermostat noting and correcting any problems Operate the unit through mechanical heating cycles from the thermostat noting and correcting any problems Operate the unit through emergency heating cycles from the thermostat noting and correcting any problems Job site has been cleaned indoor and outdoor debris removed f...

Reviews: