IR FLAME DETECTOR MODEL RIV-601P/FA
explosionproof enclosure

DESCRIPTION AND SPECIFICATIONS

All same as for RIV-601P/F model except:

•  Cast aluminium explosion-proof enclosure 

ADF-600AP

 model. 

  External grey epoxy paint RAL7000 and internal anti-condensing orange 

paint RAL2004.

•  Type of protection 

II

 2 GD Ex d 

II

C T6 Ex tb 

III

C T85°C IP66 (85°C max case 

  temperature, referred to 40°C ambient). 
•  Conforms to ATEX Directive, BVI 14 ATEX 0007 certificate.
•  Dimensions: mm. 225x255x170h main body only (mounting holes 260x220 – 

overall dimensions 290x255).

•  Weight: kg. 10,5 case only - kg. 11,5 with detector inside.
•  Sensitivity reduced to 4% of the distance.
•  M32x1.5 cable entry.

ELECTRICAL CONNECTIONS

MECHANICAL DIMENSIONS

RIV-601P/F watertight enclosure

RIV-601P/F

IR FLAME DETECTOR

85

65

70

140 39

180

125

Cable fitting M25

4 mounting through 

holes which don’t 

have any contact 

with the inside space

EN 54-10 class 1

VdS approval G 211093

0786 - CPR - 21103

RIV-601P/FA with explosionproof enclosure ADF-600AP

RIV
-601P/F

72

200

140

141

290

260

225

220

255

15

40

170

n 1 hole M32x1.5 

FIELD OF VIEW 90°

4 mounting holes 
260x220mm

Note: In the model RIV-601P/FA the detector RIV-601P/F is to be mounted inside 
the explosionproof case by the customer during the installation phase, through 
the front window, over the steel plate provided on the bottom.

STATIC OUTPUT

50mA load to +24V

TEST (24Vdc 20mA)

POWER 24Vdc ( - )

RELAY CONTACT OUTPUT
1A 30Vdc 
(L=NO, R=NC, C=COM)

POWER 24Vdc 
( + ) 13/50mA

5 sec delay time

RIV-601P/F

LED alarm

mod

L

+

R

C

T+

-

S

NPN coll 

Ground

-        +

IR FLAME DETECTOR MODEL RIV-601P/F 
watertight enclosure

 

ELECTRICAL AND GENERAL SPECIFICATIONS

•  Cast aluminium watertight case, 

IP66

 grade protection (dust and water 

spray). Explosion-proof available with the model RIV-601P/FA.

•  Power voltage 24Vdc +/-15% (20 to 28V).
•  Current consumption 13mA in stand-by (0.25W), 50mA in alarm state (max 

1.5W including 20mA for test).

•  Anti-inversion diode on +24V and + Test (

T+

).

•  Spectral response infrared 1 to 3 micron.
•  Tuned to flame pulsing frequency (flickering).
•  Field of view 90° cone. The detector can see outside the field of view or 
  indirectly by reflection, or even through smoke, with a reduced sensitivity.
•  Sensitivity 2-3% of the distance, which means that the smallest detectable 

flame size is 2-3% of the distance. For example, at 10m the smallest flame 
size is 20cm. Typical covering figure is 400 square meters at 20m distance.

•  Alarm delay time set  to 5 sec. Adjustable from 1 to 10 sec. 
  Reset is automatic. The detector turns on 5 seconds after the flame is start-

ed. As soon as the flame stops, the detector returns off.

•  Front LED lamp lights in alarm. It blinks shortly during the teletest.
•  Output on changeover SPDT relay contact rated 1A 30Vdc. 
  Other output on NPN transistor open collector rated 50mA 24Vdc, which 

goes low in alarm.

•  Built-in “Teletest” device for the remote monitoring of the detector ability. 

Needs a 24Vdc +/-15% 20mA. Built-in modulator. When the teletest circuit is 
powered, a small incandescent bulb placed near the sensor starts pulsing so 
as to simulate a flame. During the test the detector turns on for half a 

  second every 4 seconds. The teletest can be remotely controlled from the 

control panel, or can be wired for a continuous and automatic operation. 

  Control panel must recognise the short test pulses from the alarm state, 

which is steady on.

•  Electrical wiring on 7 way terminal block, plug-in type, 10 pitch, wire size 
 2,5mm

2

 max (a max 1,5mm

2

 wire gauge is suggested to avoid a difficult wire 

entry into the screw terminal).

•  Cable entry fitting M25 internal diameter 13-18mm.
•  Operating temperature   

-20  +60°C.

•  Storage temperature       

-40  +85°C.

•  Dimensions 180x85x65(H) mm (mounting holes 125x70mm).
•  Weight 700 grams.
•  Manufactured in compliance with the essential requirements of the CPR 

Regulation.

•  EN 54-10 class 1 approved, EC-certificate of conformity 
 

no. 0786-CPD-21103, VdS Approval no. G 211093.

Note:

1. It is highly recommended to connect the enclosure base to a good ground 

line using the 

ground

 terminal provided inside up on the left. Then, 

  connect base and cover using the ground terminal provided inside the 

base lower on the right and the ground terminal provided inside the cover 
lower on the left.

  All the ground terminals are signaled by ground label. 
  The ground connection must be done using a yellow-green conductor and 

a M4 double crimp eyelet.

 

 

  The yellow-green ground conductor must be longer than the other 
 conductors.

2. In order to ensure an 

IP66 protection grade

 the cover must be tightly 

closed turning the four screws provided. The suggested closing torque 
value is 1 ÷ 1,5 Nm.

Содержание GTS RIV-601F

Страница 1: ...N 54 10 class 1 rev 5 NOV18 ECOTECH GTS SRL Via del Plan del Sant 24 38012 Predaia Fraz Mollaro TN P IVA 02553340221 Tel 0463 461049 Fax 0463 461375 info ecotechgts com www ecotechgts com IR FLAME DET...

Страница 2: ......

Страница 3: ...ation with PARTIAL area coverage 11 Diagonal application with FULL area coverage 12 Vertical application of two detectors with FULL area coverage 13 Diagonal application of two detectors with FULL are...

Страница 4: ...ire detector device that responds immediately to the thermal infrared radiation emitted by fire and is tuned to the pulse frequency of the flame to ignore sun lamps and other light and infrared radiat...

Страница 5: ...tle attenuated by dust much less than light is Therefore a frequent window cleaning is not required Also smoke does not blind the detector which is operating well with fires in heavy smoke IR flame de...

Страница 6: ...y 2 3 of the distance which means that the smallest detectable flame size is 2 3 of the distance For example at 10m the smallest flame size is 20cm Typical covering figure is 400 square meters at 20m...

Страница 7: ...the top of every terminal and on the circuit board just before the connector Note 1 It is highly recommended to connect the enclosure base to a good ground line using the ground terminal provided insi...

Страница 8: ...me detector mechanical dimensions IP66 grade protection dust and water spray Dimensions 180x85x65 H mm mounting holes 125x70mm Weight 700grams 85 65 70 125 140 39 180 Cable fitting M25 RIV 601P F IR F...

Страница 9: ...inside Sensitivity reduced to 4 of the distance M32x1 5 cable entry RIV 601P F 200 140 141 290 260 225 220 255 n 1 hole M32x1 5 FIELD OF VIEW 90 15 40 170 4 mounting holes 260x220mm 245 245 86 117 23...

Страница 10: ...r during the installation by turning the one turn screwdriver potentiometer The detector field of view is a 90 cone starting at the optical window centre Outside the field of view the detector sensiti...

Страница 11: ...looking down vertically on the centre at a height that is 0 7 times the side of the area square For example from a height of 10 m a floor area of 14x14m can be controlled This sort of installation us...

Страница 12: ...areas on the corners are out The smallest detectable flame size is 20 cm on the centre 2 of 10m distance and 28cm on the border 2 of 14m distance The limit of this application could be a room 10m hig...

Страница 13: ...two times as much as under the detector corner This disadvantage must be considered when choosing this type of application Also the diagonal mounting makes the detector seeing other strong infrared l...

Страница 14: ...rformance than the C type of the previous page In the case of a room 10 m high with a floor of 14x28 m the smallest detectable flame size is 20cm on each area centre 2 of 10m distance and 28cm on each...

Страница 15: ...first case the room is 10m high and has a floor of 20x40m In the second case the room is the same but the two detectors are mounted in a slightly different position The disadvantages of the diagonal m...

Страница 16: ...revent both rain or snow to build up over the detector enclosure and to prevent as well the detector from seeing directly the sun or other strong lamps present around so as to avoid false alarms In th...

Страница 17: ...ctor Normally it is high 24V In alarm goes low 0 1V or higher depending on the load Max load 50mA to 24V One changeover SPDT relay contact on the C R L terminals rated 1A 30Vdc C R normally closed con...

Страница 18: ...r dirt build up but only the electronic circuit operation Then if the optical window is dirty the sensitivity is reduced and the fire could not be detected even if the test is ok Anywhere a small dust...

Страница 19: ...L1 line must be delayed for at least 5 10 seconds before giving a fire alarm signal when C L closes The fault warning signal must be delayed for at least 10 20 seconds before the C R closure can be c...

Страница 20: ...the detector from issuing false alarms still assuring a good sensitivity level One filter disc decreases the detector sensitivity from the standard value of 2 to 3 Then the smallest detectable flame s...

Страница 21: ...esigned for IR Flame Detector RIV 601P F mounting Both the steering arm and the base plate are made of aluminium screw parts are of stainless steel and can be used in outdoor applications Specificatio...

Страница 22: ...rev 1 DEC16 MAFP 21 GB...

Страница 23: ...rev 0 NOV11 MAFP 22 GB...

Страница 24: ......

Страница 25: ......

Страница 26: ......

Страница 27: ......

Страница 28: ...ECOTECH GTS SRL Via del Plan del Sant 24 38012 Predaia Fraz Mollaro TN P IVA 02553340221 Tel 0463 461049 Fax 0463 461375 info ecotechgts com www ecotechgts com...

Отзывы: