rev. 3 NOV18
MAFP 5-GB
IR FLAME DETECTOR MODEL RIV-601P/FA
explosionproof enclosure
DESCRIPTION AND SPECIFICATIONS
All same as for RIV-601P/F model except:
• Cast aluminium explosion-proof enclosure
ADF-600AP
model.
External grey epoxy paint RAL7000 and internal anti-condensing orange
paint RAL2004.
• Type of protection
II
2 GD Ex d
II
C T6 Ex tb
III
C T85°C IP66 (85°C max case
temperature, referred to 40°C ambient).
• Conforms to ATEX Directive, BVI 14 ATEX 0007 certificate.
• Dimensions: mm. 225x255x170h main body only (mounting holes 260x220 –
overall dimensions 290x255).
• Weight: kg. 10,5 case only - kg. 11,5 with detector inside.
• Sensitivity reduced to 4% of the distance.
• M32x1.5 cable entry.
ELECTRICAL CONNECTIONS
MECHANICAL DIMENSIONS
RIV-601P/F watertight enclosure
RIV-601P/F
IR FLAME DETECTOR
85
65
70
140 39
180
125
Cable fitting M25
4 mounting through
holes which don’t
have any contact
with the inside space
EN 54-10 class 1
VdS approval G 211093
0786 - CPR - 21103
RIV-601P/FA with explosionproof enclosure ADF-600AP
RIV
-601P/F
72
200
140
141
290
260
225
220
255
15
40
170
n 1 hole M32x1.5
FIELD OF VIEW 90°
4 mounting holes
260x220mm
Note: In the model RIV-601P/FA the detector RIV-601P/F is to be mounted inside
the explosionproof case by the customer during the installation phase, through
the front window, over the steel plate provided on the bottom.
STATIC OUTPUT
50mA load to +24V
TEST (24Vdc 20mA)
POWER 24Vdc ( - )
RELAY CONTACT OUTPUT
1A 30Vdc
(L=NO, R=NC, C=COM)
POWER 24Vdc
( + ) 13/50mA
5 sec delay time
RIV-601P/F
LED alarm
mod
L
+
R
C
T+
-
S
NPN coll
Ground
- +
IR FLAME DETECTOR MODEL RIV-601P/F
watertight enclosure
ELECTRICAL AND GENERAL SPECIFICATIONS
• Cast aluminium watertight case,
IP66
grade protection (dust and water
spray). Explosion-proof available with the model RIV-601P/FA.
• Power voltage 24Vdc +/-15% (20 to 28V).
• Current consumption 13mA in stand-by (0.25W), 50mA in alarm state (max
1.5W including 20mA for test).
• Anti-inversion diode on +24V and + Test (
T+
).
• Spectral response infrared 1 to 3 micron.
• Tuned to flame pulsing frequency (flickering).
• Field of view 90° cone. The detector can see outside the field of view or
indirectly by reflection, or even through smoke, with a reduced sensitivity.
• Sensitivity 2-3% of the distance, which means that the smallest detectable
flame size is 2-3% of the distance. For example, at 10m the smallest flame
size is 20cm. Typical covering figure is 400 square meters at 20m distance.
• Alarm delay time set to 5 sec. Adjustable from 1 to 10 sec.
Reset is automatic. The detector turns on 5 seconds after the flame is start-
ed. As soon as the flame stops, the detector returns off.
• Front LED lamp lights in alarm. It blinks shortly during the teletest.
• Output on changeover SPDT relay contact rated 1A 30Vdc.
Other output on NPN transistor open collector rated 50mA 24Vdc, which
goes low in alarm.
• Built-in “Teletest” device for the remote monitoring of the detector ability.
Needs a 24Vdc +/-15% 20mA. Built-in modulator. When the teletest circuit is
powered, a small incandescent bulb placed near the sensor starts pulsing so
as to simulate a flame. During the test the detector turns on for half a
second every 4 seconds. The teletest can be remotely controlled from the
control panel, or can be wired for a continuous and automatic operation.
Control panel must recognise the short test pulses from the alarm state,
which is steady on.
• Electrical wiring on 7 way terminal block, plug-in type, 10 pitch, wire size
2,5mm
2
max (a max 1,5mm
2
wire gauge is suggested to avoid a difficult wire
entry into the screw terminal).
• Cable entry fitting M25 internal diameter 13-18mm.
• Operating temperature
-20 +60°C.
• Storage temperature
-40 +85°C.
• Dimensions 180x85x65(H) mm (mounting holes 125x70mm).
• Weight 700 grams.
• Manufactured in compliance with the essential requirements of the CPR
Regulation.
• EN 54-10 class 1 approved, EC-certificate of conformity
no. 0786-CPD-21103, VdS Approval no. G 211093.
Note:
1. It is highly recommended to connect the enclosure base to a good ground
line using the
ground
terminal provided inside up on the left. Then,
connect base and cover using the ground terminal provided inside the
base lower on the right and the ground terminal provided inside the cover
lower on the left.
All the ground terminals are signaled by ground label.
The ground connection must be done using a yellow-green conductor and
a M4 double crimp eyelet.
The yellow-green ground conductor must be longer than the other
conductors.
2. In order to ensure an
IP66 protection grade
the cover must be tightly
closed turning the four screws provided. The suggested closing torque
value is 1 ÷ 1,5 Nm.