background image

rev. 0 NOV11

MAFP 16-GB

RIV-601P/F

IR flame detector electrical connections 

  

The electrical connections are done on 7-way screw type terminal 
block, plug in type.
Each terminal function is printed on the top of every terminal and on 
the circuit board just before the connector.
The input power voltage is 24Vdc nominal value, with an accepted 
range of 20 to 28Vdc.

The current values are rather low, typically 0.1 to 0.2 Adc. Therefore 
the wire gauge is only chosen to be strong enough, not for the rated 
current. 
A max 1,5 square mm wire gauge is suggested to avoid a difficult wire 
entry into the screw terminal.
Before turning the input power on is highly recommended to check the 
power voltage value and polarity in order to avoid damage.

Input power:

The 24Vdc power voltage must be entered into the two terminals 
marked (

 

+

 

) and (

 

-

 ). Pay attention to the polarity, even if an 

anti-inversion diode is provided on the (

 

+

 

) terminal.

Please remember that after the 24Vdc power voltage is applied the 
detector is disabled and standing by for about 10 seconds (start-up 
delay) before starting the normal operation and being able to start an 
alarm.

Output:
• 

 One static output on the “

S

” terminal from an NPN collector. 

  Normally it is high (+24V). In alarm goes low (+0.1V or higher, 
  depending on the load). Max load 50mA to +24V.
•  One changeover SPDT relay contact on the 

C-R-L

 terminals, rated 

1A 30Vdc.

 C-R

 normally closed contact. Opens in alarm.

 C-L 

normally open contact. Closes in alarm.

Test:

The 

+

 must be connected to +24V through a normally open 

pushbutton, which will be depressed for more than 5 sec in order to 
perform the 

manual test

 (see the next page). 

The 

+

 

terminal must be permanently connected to +24V if the 

automatic continuous self test

 is wanted (see the next page).

 + 

T+ S

MOD

RIV-601P/F

+ 24V

0 V 

+

-

Relay

NPN

TEST

Ground

LED alarm

delay time

               5 sec

Relay contact

Static output
50mA load 
to +24V

+ 24V
Power 

Note:

1. It is highly recommended to connect the enclosure base to a good ground line using the 

ground

 terminal provided inside up on the left. Then, 

  connect base and cover using the ground terminal provided inside the base lower on the right and the ground terminal provided inside the cover lower on the 

left.

  All the ground terminals are signaled by ground label.

The ground connection must be done using a yellow-green conductor and a M4 double crimp eyelet.

  The yellow-green ground conductor must be longer than the other conductors.

2. In order to ensure an 

IP66 protection grade

 the cover must be tightly closed turning the four screws provided. The suggested closing torque value is 1 ÷ 1,5 

Nm.

Содержание GTS RIV-601F

Страница 1: ...N 54 10 class 1 rev 5 NOV18 ECOTECH GTS SRL Via del Plan del Sant 24 38012 Predaia Fraz Mollaro TN P IVA 02553340221 Tel 0463 461049 Fax 0463 461375 info ecotechgts com www ecotechgts com IR FLAME DET...

Страница 2: ......

Страница 3: ...ation with PARTIAL area coverage 11 Diagonal application with FULL area coverage 12 Vertical application of two detectors with FULL area coverage 13 Diagonal application of two detectors with FULL are...

Страница 4: ...ire detector device that responds immediately to the thermal infrared radiation emitted by fire and is tuned to the pulse frequency of the flame to ignore sun lamps and other light and infrared radiat...

Страница 5: ...tle attenuated by dust much less than light is Therefore a frequent window cleaning is not required Also smoke does not blind the detector which is operating well with fires in heavy smoke IR flame de...

Страница 6: ...y 2 3 of the distance which means that the smallest detectable flame size is 2 3 of the distance For example at 10m the smallest flame size is 20cm Typical covering figure is 400 square meters at 20m...

Страница 7: ...the top of every terminal and on the circuit board just before the connector Note 1 It is highly recommended to connect the enclosure base to a good ground line using the ground terminal provided insi...

Страница 8: ...me detector mechanical dimensions IP66 grade protection dust and water spray Dimensions 180x85x65 H mm mounting holes 125x70mm Weight 700grams 85 65 70 125 140 39 180 Cable fitting M25 RIV 601P F IR F...

Страница 9: ...inside Sensitivity reduced to 4 of the distance M32x1 5 cable entry RIV 601P F 200 140 141 290 260 225 220 255 n 1 hole M32x1 5 FIELD OF VIEW 90 15 40 170 4 mounting holes 260x220mm 245 245 86 117 23...

Страница 10: ...r during the installation by turning the one turn screwdriver potentiometer The detector field of view is a 90 cone starting at the optical window centre Outside the field of view the detector sensiti...

Страница 11: ...looking down vertically on the centre at a height that is 0 7 times the side of the area square For example from a height of 10 m a floor area of 14x14m can be controlled This sort of installation us...

Страница 12: ...areas on the corners are out The smallest detectable flame size is 20 cm on the centre 2 of 10m distance and 28cm on the border 2 of 14m distance The limit of this application could be a room 10m hig...

Страница 13: ...two times as much as under the detector corner This disadvantage must be considered when choosing this type of application Also the diagonal mounting makes the detector seeing other strong infrared l...

Страница 14: ...rformance than the C type of the previous page In the case of a room 10 m high with a floor of 14x28 m the smallest detectable flame size is 20cm on each area centre 2 of 10m distance and 28cm on each...

Страница 15: ...first case the room is 10m high and has a floor of 20x40m In the second case the room is the same but the two detectors are mounted in a slightly different position The disadvantages of the diagonal m...

Страница 16: ...revent both rain or snow to build up over the detector enclosure and to prevent as well the detector from seeing directly the sun or other strong lamps present around so as to avoid false alarms In th...

Страница 17: ...ctor Normally it is high 24V In alarm goes low 0 1V or higher depending on the load Max load 50mA to 24V One changeover SPDT relay contact on the C R L terminals rated 1A 30Vdc C R normally closed con...

Страница 18: ...r dirt build up but only the electronic circuit operation Then if the optical window is dirty the sensitivity is reduced and the fire could not be detected even if the test is ok Anywhere a small dust...

Страница 19: ...L1 line must be delayed for at least 5 10 seconds before giving a fire alarm signal when C L closes The fault warning signal must be delayed for at least 10 20 seconds before the C R closure can be c...

Страница 20: ...the detector from issuing false alarms still assuring a good sensitivity level One filter disc decreases the detector sensitivity from the standard value of 2 to 3 Then the smallest detectable flame s...

Страница 21: ...esigned for IR Flame Detector RIV 601P F mounting Both the steering arm and the base plate are made of aluminium screw parts are of stainless steel and can be used in outdoor applications Specificatio...

Страница 22: ...rev 1 DEC16 MAFP 21 GB...

Страница 23: ...rev 0 NOV11 MAFP 22 GB...

Страница 24: ......

Страница 25: ......

Страница 26: ......

Страница 27: ......

Страница 28: ...ECOTECH GTS SRL Via del Plan del Sant 24 38012 Predaia Fraz Mollaro TN P IVA 02553340221 Tel 0463 461049 Fax 0463 461375 info ecotechgts com www ecotechgts com...

Отзывы: