rev. 0 NOV11
MAFP 16-GB
RIV-601P/F
IR flame detector electrical connections
The electrical connections are done on 7-way screw type terminal
block, plug in type.
Each terminal function is printed on the top of every terminal and on
the circuit board just before the connector.
The input power voltage is 24Vdc nominal value, with an accepted
range of 20 to 28Vdc.
The current values are rather low, typically 0.1 to 0.2 Adc. Therefore
the wire gauge is only chosen to be strong enough, not for the rated
current.
A max 1,5 square mm wire gauge is suggested to avoid a difficult wire
entry into the screw terminal.
Before turning the input power on is highly recommended to check the
power voltage value and polarity in order to avoid damage.
Input power:
The 24Vdc power voltage must be entered into the two terminals
marked (
+
) and (
-
). Pay attention to the polarity, even if an
anti-inversion diode is provided on the (
+
) terminal.
Please remember that after the 24Vdc power voltage is applied the
detector is disabled and standing by for about 10 seconds (start-up
delay) before starting the normal operation and being able to start an
alarm.
Output:
•
One static output on the “
S
” terminal from an NPN collector.
Normally it is high (+24V). In alarm goes low (+0.1V or higher,
depending on the load). Max load 50mA to +24V.
• One changeover SPDT relay contact on the
C-R-L
terminals, rated
1A 30Vdc.
C-R
normally closed contact. Opens in alarm.
C-L
normally open contact. Closes in alarm.
Test:
The
T
+
must be connected to +24V through a normally open
pushbutton, which will be depressed for more than 5 sec in order to
perform the
manual test
(see the next page).
The
T
+
terminal must be permanently connected to +24V if the
automatic continuous self test
is wanted (see the next page).
+
L
R
C
-
T+ S
MOD
RIV-601P/F
+ 24V
0 V
+
-
Relay
NPN
TEST
Ground
LED alarm
delay time
5 sec
Relay contact
Static output
50mA load
to +24V
+ 24V
Power
Note:
1. It is highly recommended to connect the enclosure base to a good ground line using the
ground
terminal provided inside up on the left. Then,
connect base and cover using the ground terminal provided inside the base lower on the right and the ground terminal provided inside the cover lower on the
left.
All the ground terminals are signaled by ground label.
The ground connection must be done using a yellow-green conductor and a M4 double crimp eyelet.
The yellow-green ground conductor must be longer than the other conductors.
2. In order to ensure an
IP66 protection grade
the cover must be tightly closed turning the four screws provided. The suggested closing torque value is 1 ÷ 1,5
Nm.