rev. 0 NOV11
MAFP 11-GB
- Vertical application with PARTIAL area coverage
When ceiling is low or not high enough for full coverage, the
centre vertical mounting is anyway used, provided only small
corner areas are out of the detector field of view, and these
small areas are not under risk of fire.
For example, a room 10m high with a floor of 16x20m is almost
completely under the detector field of view. Only four small
areas on the corners are out.
The smallest detectable flame size is 20 cm on the centre (2%
of 10m distance) and 28cm on the border (2% of 14m
distance).
The limit of this application could be a room 10m high with a
floor of 20x20m, where the cone field of view base circle
touches the floor sides. In this case the side length is 2 times
as much as the ceiling height, and the smallest detectable
flame size is 28cm in the worst case (2% of 14m distance).
RIV-601P/F
IR flame detector applications
RIV
width
length
height
Note:
Remember that the detector sensitivity is 2% of the distance, while 4% for the explosion-proof model