3.6  System parameter setting

3.6.1  Under stand-by state, to check the Inquiry interface(see3.5.2), if current displayed 

           parameter are system parameter, press 

      

 may enter to current parameter 

           setting interface.

3.6.2  On the interface of parameter setting, press 

      

or

      

 to adjust the current 

           system parameter setting value. After parameter value is set, press 

     

again  

           to save current setting value, and exit current parameter setting interface.

3.6.3  During the parameter setting , if not pressing any button within 10 seconds, system 

           automatically save current setting value , exit setting interface and return to main

           interface.

ess directly 

       

 also return to main interface.

3.7     Any pressing on the LCD controller will lighten the background light, if no any 

          other operation within 10 seconds, background light will be off.

To pr

 button

15E: 
 temperature 
sensor failure

Ambient

12

System parameter

 setting

3.5.2  On the interface of Parameter and Status inquiry , if not pressing any button within 

           10 seconds, system automatically exit the inquiry interface and return to main 

           interface, To press directly 

      

ON/OFF or 

     

 button also return to 

           main interface.

3.8  

Setting about S1 & S2 switch

       

S1 Switch---Second Set Point 

       S2 Switch----Long distance demand

  

3.8.1 Second Set Point available when S1 switch has well connected.

          At the same time, water temp set point setting decided by ambient temp, Parameter 31 and

          Parameter 32. (Both 31 & 32 Parameter would be adjusted)

          Parameter 31 (maximum setting range 50~60 

°

C) 

          Parameter 32 (minimum setting range 20~40 

°

C)  

          A. When ambient temp < 5

°

C,  set point temp refer to the data of  Parameter 31

          B. When ambient temp >15

°

C,  set point temp refer to the data of  Parameter 32

          C. When 5

°

 ambient temp 

 15

°

C, Set point temp = Data of Parameter 31- (Data of 

                parameter 31- data of parameter of 32)/(15-5)*(Ambient temp -5 )

               For example, when ambient temp is 18 deg c, Parameter 31 data is 60 deg c, Parameter 32 

               data is 20 deg c.Then set point temp =60-(60-20)/(15-5)*(18-5)

Содержание SWBM-10.5H-B/P-S

Страница 1: ...Installation Instruction Manual LOW AMBIENT HEAT PUMP WATER HEATER MODEL SWBM 10 5H B P S SWBM 17 5H B P S SWBM 35 0H B S...

Страница 2: ......

Страница 3: ...customers Product Introducing 2 Work principle 3 Performance Data 4 Dimension 5 Operation introductions 8 Wire Circuit Diagram 14 Installation instructions 16 Maintenance 20 1 CONTENTS Water heater C...

Страница 4: ...omponents without switching off the electrical supply to the unit Electric leakage switch protection device MUST be installed 3 It is forbidden to start any work on the electrical components if water...

Страница 5: ...Heat pump not only use less electricity to get heat from ambient air but are also able to combine using with solar equipment will not cause pollution and no poison gas exhausting All Round The Year Ho...

Страница 6: ...mpressor compress it the refrigerant gas became high temperature and high pressure Then the gas come into the water condensation into liquid emit a lot of condensation heat condensing heat absorbed by...

Страница 7: ...et Weight Gross Weight Unit Dimension L W H Weight kg Kpa Water pump Power Head M KW RPM dB A inch 3 m h mm mm W V PH Hz COP W W Running Current Heating A Heating Input Power W Scroll SWBM 17 5H B P S...

Страница 8: ...Water heater Dimension Measure mm The dimension for air source heat pump water heater SWBM 10 5H B P S 5 804 1510 1362 565 460 420 500...

Страница 9: ...Measure mm The dimension for air source heat pump water heater SWBM 17 5H B P S low ambient Dimension Water heater 6 1300 765 420 1370 460 500...

Страница 10: ...The dimension for low ambient air source heat pump water heater SWBM 35 0H B S Dimension Water heater Measure mm 7 1850 1580 508 1790 880 460 500...

Страница 11: ...ss to turn on or turn off the heat pump 2 1 2 After entering parameter or clock setting press once to return to main interface Start up state Stand by state 1 2 Initialization Operation introductions...

Страница 12: ...d keyboard is locked 3 2 2 Under locked state press both and at the same time for 5 seconds after Dee sound keyboard is unlocked heat pu Clock setting 3 3 Clock Setting 3 3 1 On main interface press o...

Страница 13: ...n minute 3 4 4 After setting the minutes press once to confirm and save all the Timer On setting and switch to Timer Off setting interface At this moment the hour of clock shows and flashes press or t...

Страница 14: ...31 32 Display also even system is not start up Actual testing value Actual testing value Actual testing value Actual testing value Actual testing value Actual testing value Actual testing value Actual...

Страница 15: ...or failure Ambient 12 System parameter setting 3 5 2 On the interface of Parameter and Status inquiry if not pressing any button within 10 seconds system automatically exit the inquiry interface and r...

Страница 16: ...em 1 compressor high pressure failure System 1 compressor low pressure failure System 1 compressor air exhausting temperature too high power phase failure Auxiliary heater temperature too high protect...

Страница 17: ...lve Fan Motor Swichable maghtism valve Wire Controller Transformer U CONTACTOR 1 V W YLW GRN Ambient Temp Economizer inlet Temp Economizer outlet Temp Compressor side air discharge Temp Air fin evapor...

Страница 18: ...er A B C N1 N2 N3 3 High Press Switch SYS1 High Press Switch SYS2 SYS1 Low Press Switch SYS2 Low Press Switch Electric heater protect Water flow Wire Controller C Z 1 C Z 2 C Z 3 C Z 4 C Z 5 C Z 6 C Z...

Страница 19: ...o the distance between the barriers shown in below picture pay attention to arrow direction Water tank 1Water tanks should be placed where ambient temperature is above 0 1Can be installed outdoors or...

Страница 20: ...own on the manual and in accordance with national corresponding construction standards 1Installation of water pipes should be straight and flat pipeline collocation should be rational ensure to minimi...

Страница 21: ...ck the electricity distribution System 1Check if the power supply same as shown on manual and rating label 1Check if all the power supply and control wiring are all well connected check if the wiring...

Страница 22: ...2 minutes 1 When water pump is on and the high level switch cut off if water temperature set Temperature 5 degrees shut down water supply for tanks If water tank temperature temperature 2 degrees the...

Страница 23: ...around should remain clean well ventilated Regularly clean 1 2 month the side air heat exchanger to maintain a good effect of heat exchange 7 Frequently check whether each part of the unit work normal...

Страница 24: ...Air Source Heat Pump Water Heater...

Отзывы: