INSTALLER SECTION
Use the
keys to select the
maximum allowable
airflow in heating to
the sleeping area.
UP/DOWN
Use the
keys to set the time at
which second stage
heating or cooling is
activated.
UP/DOWN
Sleeping
Airflow %
Option
Option
Heat
For options 20 - 23, use the installer test
o
imum allowable airflow.
n the following page to determine the
max
20 Maximum Airflow in Heating to Sleeping Area
19 Upstaging Time
Factory Default: 160%. Range: 100% to 160%.
Factory Default: 10 min. Range: 5 to 30 min.
NEXT
ENTER
NEXT
ENTER
Touch NEXT or ENTER.
Touch NEXT or ENTER.
Use the
keys to select the
maximum allowable
airflow in cooling to
the sleeping area.
UP/DOWN
Sleeping
Airflow %
Option
Cool
21 Maximum Airflow in Cooling to the Sleeping Area
Factory Default: 150%. Range: 100% to 160%.
NEXT
ENTER
Touch NEXT or ENTER.
Use the
keys to select the
maximum allowable
airflow in heating to
the living area.
UP/DOWN
Living
Airflow %
Option
Heat
22 Maximum Airflow in Heating to the Living Area
Factory Default: 160%. Range: 100% to 160%.
NEXT
ENTER
Touch NEXT or ENTER.
Use the
keys to select the
maximum allowable
airflow in cooling to
the living area.
UP/DOWN
Living
Airflow %
Option
Cool
23 Maximum Airflow in Cooling to the Living Area
Factory Default: 150%. Range: 100% to 160%.
NEXT
ENTER
Touch NEXT or ENTER.
Use the
key
to select OFF only if
disabling manual
airflow control. (Not
typical)
DOWN
Manual airflow control enables the homeowner
to direct more airflow to the living or sleeping
space as they desire. This option is ideal for
homeowners who have an unusual work
schedule, home office or spend more time in one
space than the other. The User Menu is used to
turn off automatic airflow control. Nighttime
Airflow option is still enabled but can be turned
off using the User Options.
Option
18 USER (Manual) Airflow Control Enabled
Factory Default: On. Range: On or Off.
NEXT
ENTER
Touch NEXT or ENTER.
Use the
keys to select the
maximum allowable
temperature
difference between
the sleeping and
living area.
UP/DOWN
Option
This is the maximum allowable temperature
difference between the sleeping and living area
temperatures. When the temperature difference is
equal to or greater than the allowed differential,
the airflow is adjusted.
24 Maximum Temperature Differential
o
Factory Default: 2 F.
o
o
Range: 0 to 10 F
25 Factory Restore
NEXT
To restore factory
settings, touch the
key to display
YES then touch
ENTER.
UP
Option
WARNING! Factory Restore resets ALL settings.
NEXT
Option
NEXT
ENTER
ENTER
Touch NEXT or ENTER.
ENTER
To exit this option,
touch
or
NEXT
ENTER, or the hidden
Back key.
Manual airflow control enables the homeowner to direct more
airflow to the living or sleeping space as they desire. This option
is ideal for homeowners who have an unusual work schedule,
home office or spend more time in one space than the other.
Page 8 of 16