- 31 -
Detection of flow switch Ground-source pump to run start compressor
1
.
4 Four-way valve closed
。
Ground-source pumps compressors in advance
〖
C7
〗
seconds
to open
。
When Compressor is stopped ,Ground-source pumps stop delay 1
.
5 air-conditioning
pump has been running
2
﹑
Air-conditioner heating conditions
(
TI for the return Air-conditioner water temperature
)
2.
1
﹑
Compressor start Conditions
:
□
TI
≤〖
P2
〗
start compressor;
2
﹑
2 Compressor stop Conditions
:
□
TI
≥〖
P2
〗
stop compressor;
2
﹑
3 running heating Process
Select the heating mode startup Air-conditioning pumps to run
Four-way valve to run section of flow switch electric heating run
Ground-source pump to run start compressor
2.4 Air-conditioning electric heating run
□
When the 5
℃≤〖
P2
〗
-TI
,
Air-conditioning Electric heating run
。
□
When the 5
℃
〉〖
P2
〗
-TI
〉
2
℃
,
To maintain the status
。
□
When the
〖
P2
〗
-TI
〈
=2
℃,
Air-conditioning Electric heating stop
。
2
.
5 Four-way valve run
。
Ground-source pumps compressors in advance
〖
C7
〗
seconds
to open
。
When Compressor is stopped ,Ground-source pumps stop delay 2
.
6 air-conditioning
pump has been running
3
﹑
Air-conditioner cooling and heating water conditions
3
.
1 Compressor Ibid (1
﹑
air conditioning cooling running) 3
.
2 conditioning pump
has been running
3
.
3 Hot water pump operating conditions( TS for the tank water temperature)