- 30 -
Parameter Name
Cell
number
Factory sets
Max
Min
time for the duration of protection
CC
3 Seconds
10 Seconds
1 Seconds
time of flow switch detection time
continuously
Cd
10 Seconds
30 Seconds
1 Seconds
Interval of compressor start
CE
30 Seconds
90 Seconds
10 Seconds
The parameter of defrost
Parameter Name
Cell
number
Factory sets
Max
Min
Enter the defrost of the longest
cumulative time
d1
4 hours
12 hours
1 hour
Compressor enter the defrost of
the cumulative time firstly
d2
40minutes
99 minutes
20 minutes
defrost of the longest time
d3
8 minutes
15 minutes
2 minutes
Enter the condition of the
outdoor coil temperature
d4
-3
℃
0
℃
-15
℃
Exit the condition of the outdoor
coil temperature
d5
15
℃
20
℃
0
℃
5
.
.
.
.
control method
1
、
Air-conditioner cooling conditions
(
TI for the inlet Air-conditioner water temperature
)
1.
1
﹑
Compressor start Conditions
:
□
TI
≥〖
P1
〗
,start compressor;
1.
2
﹑
Compressor stop Conditions
:
□
TI
≥〖
P1
〗
,stop compressor;
1
.
3
﹑
Running cooling Process
Select the cooling mode startup Air-conditioning pumps to run