Ecoflam Multiflam 500.1 PR Скачать руководство пользователя страница 3

pag.3

LB1292   

MULTIFLAM 500.1 PR - 600.1 PR 

techniques for energy saving

CONNECTION TO THE GAS PIPELINE 

Once connected the burner to the gas pipeline, it is necessary to control that this last is perfectly sealed. Also verify that the
chimney is not obstructed. Open the gas cock and carefully bleed the piping through the pressure gauge connector, then check
the pressure value trough a suitable gauge. Power on the system and adjust the thermostats to the desired temperature. When
thermostats close, the sealing control device runs a seal test of valves; at the end of the test the burner will be enabled to run the
start-up sequence.

ELECTRICAL CONNECTIONS

All burner motors are tested at 400 V 3phase at 50 Hz, whilst auxiliaries are tested at 230V 1phase at 50 Hz.
Should it be necessary to power the burners at 230V/50Hz 3phase without neutral, carry out the necessary modifications accor-
ding to the burner’s wiring diagram, and check that the thermal relay is within the absorption field of the motor.

BURNER START-UP

Before starting the burner, make sure it is mounted correctly. Then check connections are correct according to the
diagram and piping is appropriate to the system. Before connecting the burner to the electricity supply, make sure
voltage corresponds to burner plate data. The connection diagram and start-up cycle are shown separately. For
wiring from control box to burner, see the enclosed connection diagram. Pay particular attention to neutral and
phase connections : never exchange them!. Vent air and impurities of gas pipe. Check gas pressure conforms to the
limits stated on the burner plate when connecting a master gauge to the test port provided
on the burner. Blower motor starts and pre-purging begins. Since pre-purging has to be car-
ried out with the max. air delivery, the burner control circuit turns the air damper to the
max. delivery position by the air servocontrol in approximately 30 seconds time. When the
servocontrol is fully open, a signal to the electronic control unit starts the 66 seconds pre-
purge cycle. At the end of the prepurging time, the air servocontrol gets to the Low Flame
position so that burner ignition is ensured at min. output. Simultaneously the ignition transformer receives voltage
and after 3 seconds (pre-ignition) opens the pilot gas valve. Fuel flows to the combustion head and ignites. Two
seconds after pilot gas valves have opened, the ignition transformer is excluded from the circuit. In case of no igni-
tion the burner goes to lock-out within two seconds. After 6 sec. open the working gas valve, governed by the gas
firing butterfly valve.Now the burner is operating at the min. firing rate (about 30% of the max. firing rate). The air
servocontrol runs at the Low Flame position and in case the temperature control has to be set at the max. output it
goes to a fully open position of air damper and butterfly valve. During the burner-off periods the air damper closes
up fully.

0

1

2

0 - STOP
1 - GASOLIO
2 - GAS

ADJUSTING THE COMBUSTION PROCESS

IMPORTANT:

to obtain the right adjustment of the combustion and thermal capacity it is important to analyze

the reducts of combustion with the aid of suitable instruments. The combustion and thermal capacity adjustment is
done simultaneously, together with the  analysis of the products of combustion, making sure that the measured
values are suitable and that they comply with current safety standards. On this matter, please refer to the table and
figure below. 

THESE OPERATIONS MUST BE DONE BY PROFESSIONALLY-QUALIFIED TECHNICIANS.

NOTE: 

ALL SAFETY DEVICES (AIR PRESSURE SWITCH, MINIMUM GAS PRESSURE SWITCH, GAS

SOLENOID VALVES AND GAS GOVERNOR) SHALL BE DULY SEALED AFTER CALIBRATION AND
BURNER START UP BY ECOFLAM’S TECHNICIANS.

Heavy oil

GAS TRAIN INSTALLATION

Max. pressure 50 mbar

4

4   Pilot gas valve
5 - Gas governor and filter (Optional)
6 - Min. gas pressure switch
7 - Leakage control device (Optional)
8 - Gas valve

1

2

3

5

6

7

8

1 - Main gas pipe
2 - Ball valve
3 - Antivibration coupling
4 - Pilot gas valve
5 - Gas governor and filter
6 - Gas pressure switch
7 - Leakage control
8 - Working gas valve

Содержание Multiflam 500.1 PR

Страница 1: ...G A S T E C LB1292 01 10 2003 Multiflam 500 1 PR Multiflam 600 1 PR Heavy oil Natural Gas 500 mbar MODEL techniques for energy saving GAS HEAVY OIL DUAL BURNERS ...

Страница 2: ...age 50 Hz V 230 400 230 400 Motor kW 11 15 Rpm N 2800 2800 Fuels Nat Gas LHV 35 9 Mj Nm3 8 570 kcal Nm3 Heavy oil 9 800 kcal kg max viscosity 50 E a 50 C mbar 1500 2000 2500 3000 3500 4000 4500 5000 5500 10 12 14 16 1000 18 20 22 2 4 kW 6000 0 2 4 6 8 500 MULTIFLAM 500 1 M U LTIFLA M 600 1 WORKING FIELDS Burner output Backpressure in combustion chamber E D D1 F G C B A I L M H 1068 600 SUNTEC SUNT...

Страница 3: ... servocontrol is fully open a signal to the electronic control unit starts the 66 seconds pre purge cycle At the end of the prepurging time the air servocontrol gets to the Low Flame position so that burner ignition is ensured at min output Simultaneously the ignition transformer receives voltage and after 3 seconds pre ignition opens the pilot gas valve Fuel flows to the combustion head and ignit...

Страница 4: ... Fan motor Air Switch Ignition transformer Gas valve Min max capacity enabling device Air damper Gas damper Flame detector Cut out pilot lamp Normal operating cycle Operating cycle in the event of ignition failureNormal operating cycle ADJUSTING THE PRESSURE REGULATOR The pressure regulator complete with its incorporated filter must be installed to avoid conta minants reaching the gas valve It is ...

Страница 5: ...d pilot right on the device lights up The flame control device starts the burner fan to carry out prewashing of the combustion chamber checking fan air pressure via the air pressure switch After preventilation the ignition transformer starts operating generating a spark between the electrodes and simultaneously the gas valves open safety gas valve VS and first stage operating valve VL If the flame...

Страница 6: ...e measured at pressure port E must be within the limits of the pressu re switch working range If not loose the locking nut of screw F and gradually turn the same clockwise to reduce the pressure counterclockwise to increase At the end tighten the locking nut 2 5 5 10 15 50 25 3 5 30 40 45 20 0 4 0 6 0 9 3 0 1 5 2 1 1 8 2 4 2 7 1 2 I L M N A B C D E F G H Gas pressure switch Air pressure switch Par...

Страница 7: ...iate gas flow rates see figure detail 3 using a suitable Allen wrench change the position of the cam guide blade if you screw it down the flow rate is reduced if you unscrew it the flow rate increases The ionization current is checked by inserting a microammeter with an end of scale of 50 µA d c in series with the ionization probe A faulty position of the electrode can lead to a reduction in the i...

Страница 8: ...normally always connected The pump starts to send oil the head has already been heated by its cartridge O and therefore has no residue of cold dense oil which flows from the tank to the head and then to the return line of the ring When the head thermostat reaches the set value usually about 70 30 C the cycle starts properly and the control programmer enables start up The servomotor sets itself at ...

Страница 9: ...V 50Hz WARNING For a correct working of the pump verify what follows Pump SUNTEC TA C40105 Oil temperature at the pump Max 140 C Maximum allowable pressures Max 5 bar on inlet PUMP S PRESSURE OIL TEMPERATURE DIAGRAM Pump inlet pressure the vaporisation of light fraction of heated heavy oil causes premature pump wear to avoid this use the inlet pressures shown in the graph 1 2 3 4 5 0 6 50 100 150 ...

Страница 10: ...water Drawing for heavy fuel oil up to 50 E at 50 C Hot water Return hot water pipe hot water pipe oil pipe oil pipe heating cable insulation section 1 Burner 2 Tank 3 Heater 4 Safety operation thermostat 5 Level switch 6 7 Filter 8 Load pumps 9 Holding basin 1 Burner 2 Tank 3 Heater 4 Safety operation thermostat 5 Level switch 6 Self cleaning filter 7 Heating coil 8 Load pumps 9 Ring pumps 10 Reg...

Страница 11: ...aried by acting on the nozzle through the pressure in the return line Max oil supply is therefore reached when the pressure in the pump line is about 30 bar and the return line is fully closed min oil supply when the return line is fully open see also diagram BERGONZO Relevant pressure readings in the return line are as follows return oil pressure has to be measured on M pressure gauge max oil sup...

Страница 12: ...r energy saving I H E G N A D F Q O P PRE PURGING PHASE LEGEND A Solenoid valve N C D Regulator E Tank F Anti gas valve G Resistance of the preheather H Pipe filter I Oil pump N Manometr O Resistance of combustion head P Oil temperature sensor Q Oil nozzle ...

Страница 13: ... press key F the led Out 1 starts to flash if You need to modify minimum oil temperature press increase or decrease button after confirm the new value pressing again F if You need to modify an other temperature press again F untill You the relevant led flashes Please take care if key F is pressed for a too long time You enter in configuration level phase1 see CF1 on the display these parameters ar...

Страница 14: ...wn out The control box is faulty THE BURNER RUNS THE PREPURGING AND SWITCHES TO LOCKOUT AT THE END OF CYCLE Check the fan and the air pressure Check the air pressure switch Control box faulty Ignition transformer faulty Check the ignition cable Electrodes are dirty or in wrong position Nozzles are clogged or worn Filters are clogged Light oil pressure is too low Combustion air s flow rate too high...

Страница 15: ... AFTER FEW MOMENTS Check gas governor and gas filter Check gas pressure through a manometer Check ionization value min 70 µA THE BURNER DOES NOT SWITCHES TO HIGH FLAME Manual selector switch in wrong position Faulty control box High flame solenoid valve s coils faulty Air damper s jacket faulty or wrongly adjusted ...

Страница 16: ...e principali Ecoflam S p A via Roma 64 31023 RESANA TV Italy tel 0423 715345 r a telefax 0423 715444 Italy 480009 Export 480873 715538 http www ecoflam it e mail ecoflam ecoflam it ECOFLAM S p A reserves the right to make any adjustments without prior notice which it considers necessary or useful to its products without affecting their main features ...

Отзывы: