pag.15
LB1292
MULTIFLAM 500.1 PR - 600.1 PR
techniques for energy saving
THE BURNERS IGNITES BUT SWITCHES TO LOCKOUT AFTER FEW MOMENTS:
Check gas governor and gas filter.
Check gas pressure through a manometer.
Check ionization value (min. 70 µA).
THE BURNER DOES NOT SWITCHES TO HIGH FLAME:
Manual selector switch in wrong position.
Faulty control box. High flame solenoid valve’s coils faulty.
Air damper’s jacket faulty or wrongly adjusted.