Multiflam 300.1 - 400.1 PR/PR
EN
ADJUSTMENT OF FUEL TEMPERATURE
Increase key
Decrease key
“Function” key
Display
The display shows oil temperature.
The 4 leds are related to the following functions:
Out 1: contact driving working heaters. Out 2: contact driving upper heaters KMRL1. Out 3: contact driving upper
heaters KMRL2. Out 4: Burner start driving contact (as the oil reaches this temp the pump is activated).
- The temperatures are already properly Factory setted :Out 1(
113°
)- Out 2(
115°
)- Out 3(
120°
)- Out 4(
105°
).
- To modify factory temperature setting act as follows:
- press key “
F
”.
- the led Out1 starts to flash, if You need to modify minimum oil temperature press increase or decrease button, after
confirm the new value pressing again “
F
”.
- if You need to modify an other temperature press again “
F
” untill You the relevant led flashes.
Please take care: if key “
F
” is pressed for a too long time, You enter in “configuration level” phase1, (see “CF1” on the
display); these parameters are Factory setted and they have not to be modified: if You enter this function – You see CF1
flashing on the display – wait 10 seconds untill the regulator automatically goes out from “configuration level”.
Содержание Multiflam 300.1
Страница 85: ...85 420010309500 Multiflam 300 1 400 1 PR PR RU SUNTEC TA C4 1 2 3 4 5 6 1 2 5 6 3 4 0 45 22 25 3 T...
Страница 87: ...87 420010309500 Multiflam 300 1 400 1 PR PR RU 50 E 50 C 1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 9 10 11 50 E 50 C...
Страница 88: ...88 420010309500 Multiflam 300 1 400 1 PR PR RU 5 fig B...
Страница 90: ...90 420010309500 Multiflam 300 1 400 1 PR PR RU F I H E G N A D Q O P D E F G I N O P Q...
Страница 96: ...96 420010309500 Multiflam 300 1 400 1 PR PR RU 1 2 CO2 9 5 9 8 CO 75 ppm C 0 70 A 2 3 2 3 2 3 2 3...