Installation, Operation & Maintenance Manual
E
coer
96%
A
F
UE
Gas Furnace
| 41
E
coer
I
nc
.
|
07-2021
Data subject to change
Input
Output
Nominal
Air
fl
ow
MAX. Unit
Amps
AFUE
Air Temp. Rise
Max.
Over-Current
Protection
Min. Wire Size
(AWG) @ 75 ft
Max. Outlet Air Temp
MBH
kW
MBH
kW
CFM
° F
° C
Amps
° F
° C
60B3
17.6
57
16.7
1200
8
96
30-60
17-33
15
14
160
71
80B3
23.4
76
22.3
1200
8
96
35-65
19-36
15
14
165
74
80C4
23.4
76
22.3
1600
7.8
96
35-65
19-36
15
14
165
74
100C5
29.3
95
27.8
2000
11.5
96
35-65
19-36
20
14
165
74
100D5
29.3
95
27.8
2000
10.5
96
35-65
19-36
20
14
165
74
120D5
35.2
106.5
31.2
2000
10.5
95
40-70
22-39
20
14
170
77
Table 17
Ratings & Physical / Electrical Data
Annual Fuel Utilization Ef
fi
ciency (AFUE) numbers are determined in accordance with DOE Test procedures.
National Electrical Code (NFPA-70-latest edition) and all local codes.
The furnace shall be installed so that the electrical components are protected from water.
Optional Switch Positions
DIP Switch (SW)
NOMINAL
(MINUTES)
SW1-1
SW1-2
OFF
OFF
OFF*
ON
OFF
10
OFF
ON
AUTO
ON
ON
20
Table 18
W2
Delay
* The factory default settings
DIP Switch (SW)
NOMINAL
(SECONDS)
SW1-3
SW1-4
OFF
OFF
90
ON
OFF
120
OFF
ON
150
ON
ON
180*
Table 19
Heat Off Delay
* The factory default settings
DIP Switch (SW)
NOMINAL
(SECONDS)
SW3-1
SW3-2
OFF
OFF
60
ON
OFF
90*
OFF
ON
120
ON
ON
150
Table 20
Cool Off Delay
* The factory default settings