07-2021
Data subject to change
Furnace
size
Return-air
inlet
Speed
External static pressure (in. WC)
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
100C
Bottom or
Sides
H
CFM
2195 2158 2116 2072 2031 1985 1940 1896 1852 1862
Temp Rise-1st stage
--
--
--
--
--
--
--
--
--
--
Temp
Rise-2nd
stage 40.3 41.0 41.8 42.7 43.6 44.6 45.6 46.7 47.8 47.5
Mid-H
CFM
2008 1963 1924 1882 1836 1791 1744 1697 1648 1603
Temp Rise-1st stage
--
--
--
--
--
--
--
--
--
--
Temp
Rise-2nd
stage 44.1 45.1 46.0 47.0 48.2 49.4 50.8 52.2 53.7 55.2
Mid
CFM
1753 1709 1666 1627 1573 1530 1487 1444 1395 1347
Temp
Rise-1st
stage --
--
--
35.4 36.6 37.6 38.7 39.9 41.3 42.7
Temp
Rise-2nd
stage 50.5 51.8 53.1 54.4 56.3 57.9 59.5 61.3 63.5 65.8
Mid-L
CFM
1447 1388 1338 1286 1241 1186 1137 1083 1029 983
Temp
Rise-1st
stage 39.8 41.5 43.0 44.7 46.4 48.5 50.6 53.2 55.9 58.5
Temp Rise-2nd stage
61.2
63.8
--
--
--
--
--
--
--
--
Low
CFM
1089 1021 946 883 820 751 685 625 565 520
Temp Rise-1st stage
52.8
56.4
60.8
--
--
--
--
--
--
--
Temp Rise-2nd stage
--
--
--
--
--
--
--
--
--
--
100D
Bottom or
Sides
H
CFM
2283 2239 2193 2143 2095 2049 1998 1947 1897 1847
Temp Rise-1st stage
--
--
--
--
--
--
--
--
--
--
Temp
Rise-2nd
stage 38.8 39.5 40.4 41.3 42.3 43.2 44.3 45.5 46.7 48.0
Mid-H
CFM
2086 2038 1988 1942 1889 1841 1792 1745 1695 1637
Temp Rise-1st stage
--
--
--
--
--
--
--
--
--
--
Temp
Rise-2nd
stage 42.4 43.5 44.5 45.6 46.9 48.1 49.4 50.7 52.3 54.1
Mid
CFM
1813 1760 1711 1657 1609 1560 1506 1453 1402 1350
Temp
Rise-1st
stage --
--
--
--
35.8 36.9 38.2 39.6 41.0 42.6
Temp
Rise-2nd
stage 48.8 50.3 51.8 53.4 55.0 56.8 58.8 60.9 63.1 --
Mid-L
CFM
1487 1417 1360 1296 1241 1183 1123 1064 1005 941
Temp
Rise-1st
stage 38.7 40.6 42.3 44.4 46.4 48.7 51.3 54.1 57.2 61.1
Temp Rise-2nd stage
59.5
62.5
--
--
--
--
--
--
--
--
Low
CFM
1122 1036 977 889 802 731 646 586 532 485
Temp Rise-1st stage
55.6
58.9
64.7
--
--
--
--
--
--
--
Temp Rise-2nd stage
--
--
--
--
--
--
--
--
--
--
120D
Bottom or
Sides
H
CFM
2290 2253 2213 2170 2127 2080 2031 1985 1937 1888
Temp Rise-1st stage
--
--
--
--
--
--
--
--
--
--
Temp
Rise-2nd
stage 46.4 47.2 48.0 49.0 50.0 51.1 52.3 53.5 54.9 56.3
Mid-H
CFM
2079 2037 1993 1950 1907 1856 1813 1767 1726 1675
Temp Rise-1st stage
--
--
--
--
--
--
--
--
40.0
41.2
Temp
Rise-2nd
stage 51.1 52.2 53.3 54.5 55.7 57.3 58.6 60.1 61.6 63.4
Mid
CFM
1809 1764 1719 1668 1620 1572 1528 1487 1432 1364
Temp
Rise-1st
stage --
--
40.2 41.4 42.6 43.9 45.2 46.5 48.2 50.6
Temp
Rise-2nd
stage 58.7 60.2 61.8 63.7 65.6 67.6 69.6 --
--
--
Mid-L
CFM
1489 1429 1373 1311 1265 1208 1137 1083 1032 972
Temp
Rise-1st
stage 46.4 48.3 50.3 52.7 54.6 57.2 60.7 63.8 66.9 --
Temp Rise-2nd stage
--
--
--
--
--
--
--
--
--
--
Low
CFM
1123 1051 1352 899 814 741 688 605 551 507
Temp Rise-1st stage
61.5
65.7
--
--
--
--
--
--
--
--
Temp Rise-2nd stage
--
--
--
--
--
--
--
--
--
--
Table 4
Air Delivery - CFM (Without Filter) * **
* A
fi
lter is required for each return air inlet. This table shows the air
fl
ow
performance without a
fi
lter. To determine air
fl
ow performance with a
fi
lter, if a
3/4 inch (19 mm) washable media
fi
lter is used, assume an additional 0.1 in. WC
available external static pressure.
** The manufacturer default fan settings are based on model, refer to Table 24.