Side A
Side B
0548-990/52g
Page 62 of 98
Mounting and operating instructions
Interior side
Exterior side
6.3
Interlock operation
Procedure:
Note:
Both installations must be plugged
into resp. out of the same power
supply.
1. Connect both control units by means of the
CAN cable (by plugging it into the socket
X117).
2. Normal commissioning of both drive me
-
chanisms.
3. Configuration of the drive mechanism for
the exterior door (A):
• InterL = SideA
4. Configuration of the drive mechanism for
the interior door (B):
• InterL = SideB
Control:
1. Check the display of the Master control unit to see if a small black (w) is visible on the first
level (connection existing).
Note:
A small white (w) indicates: Missing connection.
2. Transmit a Key command to the exterior door (A):
• On the display a big black (W) appears (door is not closed).
• While the exterior door (A) is open, transmit a Key command to the interior door (B) (the
latter must not be opened).
3. Transmit a Key command to the interior door (B):
• On the display a big black (W) appears (door is not closed).
• While the interior door (B) is in the open position, transmit a Key command to the exterior
(A) (the latter must not be opened).
Note:
The parameters ILAuto, ILExit and ILNigt enable you to configure the operating modes
in which the interlock system shall be active.