Eco Pacific/Super Star- Installation and Service Instructions 20173
10
•
Ductwork sized adequately and correctly installed for smooth air flow without sharp bends?
•
Make sure gas is open, power is on, and thermostat is on with pre-set temperature higher
than the room temperature to call for heat.
Operating Instructions
The
‘Super Star’ heater does not have a standing pilot rather it is equipped with an energy saving
electronic ignition device, which automatically lights the burner when the thermostat calls for heat.
Thermostat calls for heat when the pre-set temperature is set higher than the room temperature.
Do not try manually lighting burners with a spark, match, or other flame source as it could be
dangerous, and will void any given warranty.
Preliminary
Set the wall thermostat to the “OFF” position.
Open duct vents in rooms.
Check gas supply is turned on at gas-cock.
Lighting Instructions
Step 1.
Check that the thermostat is set to “OFF”.
Step 2. Turn the 240 VAC
power “ON” at the GPO connected to the unit.
Step 3.
Turn the thermostat to “ON” and to a temperature above ambient room
temperature. Unit should ignite in approximately 30 seconds.
Step 4.
For natural gas the heater will attempt ignition three times and should ignite.
However, it attempts ignition again if the flame is lost due to some reason. The
PCB on the heater rechecks ignition every hour then after.
Normal Sequence of Events for operation
a. When the thermostat is turned on it calls for heat.
b. The appliance control enters a pre purge period of about 20 seconds by running the
combustion fan.
c. A direct spark ignitor will be energised to ignite the gas after the pre-purge period.
d. Simultaneously the main gas valve opens.
e. The burners will light, and the flame sensor will detect the presence of the flame. The
ignitor will de-energise after the flame is sensed. If the flame sensor does not detect the
presence of the burner flame, the gas valve will close.
f.
The room fan will come on 20 seconds after the flame is established.
g. The furnace will remain in operation until the pre-set temp at the thermostat is reached.
h. Once the thermostat is satisfied, the gas valve will close, and approximately 35 seconds
after cooling the heat exchanger, the supply air fan will turn off.
If the unit does not ignite-
Step 5.
Turn the thermostat to “OFF” for 3 seconds, then back on again.
Step 6.
Turn the thermostat to “ON”. Unit should ignite in approximately 20 seconds.
Check the battery condition, if fitted.