INSTALLATION 

5  

  

For parts or assistance, call ECO-FLO Customer Service at 1-877 326-3561

Always install a union in the discharge 

line, just above the sump pit to allow for 

easy removal of the pump for cleaning 

or repair. 
A check valve must be used in the 

discharge line to prevent back flow of 

liquid into the basin. The check valve 

should be a free flow valve that will eas-

ily pass solids.
CAUTION: For best performance of 
check valves when handling solids 

install in a horizontal position or at an 

angle of not more then 45°. Do not in-

stall check valve in a vertical position as 

solids may settle in valve and prevent 

opening start-up. 
When check valve is used, drill a relief 

hole 3/16” in diameter in the discharge 

pipe. This hole should be located be-

low the floor line between the pump 

discharge and the check valve. Unless 

such a relief hole is provided, the pump 

could “air-lock” and will not pump water 

even though it will run. 
A gate valve should follow the check 

valve to allow periodic cleaning of the 

check valve or removal of the pump. 
The remainder of the discharge line 

should be as short as possible with a 

minimum of turns to minimize friction 

head loss. Do not restrict the discharge 

to sizes below 2’. 
Sewage and effluent applications will 

require a separate sump vent. A con-

nection is provided on top of the sump 

or cover which must be piped to the 

existing building vent or extended out-

side with its own standpipe.

For automatic operation, pump must be plugged or wired into re-

mote float switch or liquid level controller. Installation instructions 

included with switches and controllers should be referred to for 

installation.
Pump will run continuously if plugged directly into an electrical out-

let. Care should be taken to prevent pump running in a dry sump. 
Pump must be installed in a suitable gas tight basin which is at 

least 24” in diameter and 30” deep and vented in accordance with 

local plumbing codes. Pump must be placed on a hard level sur-

face. Never place pump directly on clay, earth or gravel surfaces. 
Pump can be installed with ABS, PVC, polyethylene or galvanized 

steel pipe. Proper adapters are required to connect plastic pipe to 

pump.

Air bleed hole

.

To control panel

Check valve

Gate valve

Union

Discharge pipe

Vent

Содержание ESE40W

Страница 1: ...Owner s Manual ESE Series Cast Iron Sewage Pumps General Safety 2 Specifications 3 Installation 4 5 Troubleshooting 6 Repair Parts 7 Warranty 8 TABLE OF CONTENTS...

Страница 2: ...avoided will result in death or serious injury Indicates a hazard which if not avoided could result in death or serious injury Indicates a hazard which if not avoided could result in minor or moderate...

Страница 3: ...struction Impeller Length Pumped ESE40M 4 10 115 1 11 0 6600 26 Cast Iron Thermoplastic 20 2 ESE40W 4 10 115 1 11 0 6600 26 Cast Iron Thermoplastic 20 2 ESE50M 1 2 115 1 12 0 7800 27 Cast Iron Thermop...

Страница 4: ...nd or severe damage to pump and will void the warranty a Using an extension cord b Cutting off the ground pin or using an adapter fitting c Working on pump or switch while plugged in d Removing motor...

Страница 5: ...emoval of the pump The remainder of the discharge line should be as short as possible with a minimum of turns to minimize friction head loss Do not restrict the discharge to sizes below 2 Sewage and e...

Страница 6: ...tart and stop several times by plugging in and unplugging cord Check for clogged vent hole in pump case Vertical pumping distance is too high Reduce distance or change the discharge fitting of the pum...

Страница 7: ...any alleged defect Manufacturer will subsequently take corrective action as promptly as reasonably possible No requests for service will be accepted if received more than 30 days after the warranty ex...

Отзывы: