Modbus Read, Write and Override Parameters plus Exception Codes
106
UDC2500 Universal Digital Limit ControllerProduct Manual
8/05
10.4.6 Alarms
Table 10-8 lists all the register addresses and ranges or selections for the function
parameters in Set-up Group Alarms.
Table 10-8 Set-up Group – Alarms
Parameter
Description
Register
Address
Data
Type
Access
Data Range or
Enumerated Selection
Hex
Decimal
Alarm 1 Setpoint 1
Type
008C 140
INT R/W
0 = None
1 = Not Used
2 = Not Used
3 = PV
4 = Deviation
5 = Not Used
6 = Alarm on Shed
7 = Not Used
8 = Not Used
9 = Not Used
10 = T/C Warning
11 = Failsafe or T/C Fail
12 = PV Rate of Change
13 = Alarm on Digital
Input
Alarm 1 Setpoint 1
Value
0009
009
FP
R/W
Within the range of
selected parameter or PV
span for deviation alarm
Alarm 1 Setpoint 2
Type
008E 142
INT
R/W
Same as 140
Alarm 1 Setpoint 2
Value
000A 010
FP
R/W
Within the range of
selected parameter or PV
span for deviation alarm
Alarm 2 Setpoint 1
Type
0090
144
INT
R/W
Same as 140
Alarm 2 Setpoint 1
Value
000B 011
FP
R/W
Within the range of
selected parameter or PV
span for deviation alarm
Alarm 2 Setpoint 2
Type
0092
146
INT
R/W
Same as 140
Alarm 2 Setpoint 2
Value
000C 012
FP
R/W
Within the range of
selected parameter or PV
span for deviation alarm
Содержание UDC2500 Limit
Страница 1: ...Eclipse Universal Digital Controller UDC2500 Limit Control Model 08 2005 Information Guide 925 1...
Страница 2: ...ii UDC2500 Universal Digital Limit ControllerProduct Manual 8 05...
Страница 10: ......
Страница 76: ...Input Calibration 66 UDC2500 Universal Digital Limit ControllerProduct Manual 8 05...
Страница 126: ......
Страница 127: ......
Страница 128: ......