Operating the Limit Controller
48
UDC2500 Universal Digital Limit ControllerProduct Manual
8/05
Table 4-1 Procedure to Enter a Security Code
Step
Operation
Press
Result
1
Enter Set Up
Mode
Setup
Setup
Upper Display
=
SET UP
Lower Display
=
LOCK
2
Select any Set
Up Group
Function
Function
Function
Upper Display
=
0
Lower Display
=
SECUR
3
Security Code
Entry
or
To enter a four digit number in the upper display
(0001 to 9999)
This will be your security code.
4.4 Lockout Feature
Introduction
The lockout feature in the UDC2500 is used to inhibit changes (via keyboard) of certain
functions or parameters by unauthorized personnel.
Lockout levels
There are different levels of Lockout depending on the level of security required. These
levels are:
•
NONE
No Lockout. All groups Read/Write.
•
CAL
All groups Read/Write except Calibration
•
CONF
Configuration parameters are Read only. No writes permitted.
Calibration Group is not available.
•
+SP
Only the Lockout group is available for Read/Write.
Setpoint value is Read Only.
See
Subsection 3.4- Lockout Parameters Set Up Group
prompts to select one of the
above.
Key error
When a key is pressed and the prompt “Key Error” appears in the lower display, it will be
for one of the following reasons:
• Parameter not available or locked out
• Not in setup mode, press
SET UP
key first
Содержание UDC2500 Limit
Страница 1: ...Eclipse Universal Digital Controller UDC2500 Limit Control Model 08 2005 Information Guide 925 1...
Страница 2: ...ii UDC2500 Universal Digital Limit ControllerProduct Manual 8 05...
Страница 10: ......
Страница 76: ...Input Calibration 66 UDC2500 Universal Digital Limit ControllerProduct Manual 8 05...
Страница 126: ......
Страница 127: ......
Страница 128: ......