Modbus RTU Function Codes
8/05
UDC2500 Universal Digital Limit ControllerProduct
Manual
91
Data Byte Count
The Data Byte Count is the number of data bytes of the
sub response
including the
Reference Type but not including itself. A floating point sub response has four bytes of
data and one byte representing the reference type making the data byte count equal to
five.
Reference Type Definitions
The Reference Type definition is always 06.
See examples in Subsection 9.3.1
File Number
The file number word contains the register number from the register address structure
tables on page 3. Although the register address structure tables indicate up to 13 data
registers are available for access, only register address 3 is currently supported.
Register Address
The register address word represents the tag ID number for the parameter(s) being
accessed. The register address word is made up of two bytes—the MSB = 00 always. The
LSB contains the tag ID number. The tag ID numbers represent the parameter’s register
address(es). See
Section 3
for the tag ID numbers.
Table 9-3 Register Address Format for Function Code 20
Register
Address(es)
(Decimal)
Register
Address(es)
(Hex)
Format
001 to 125
0001 to 007D
analog
formatted data
(2 registers – IEEE 32-bit floating point)
128 to 255
0080 to 00FF
integer
formatted data
(1 register – 16-bit integer)
Содержание UDC2500 Limit
Страница 1: ...Eclipse Universal Digital Controller UDC2500 Limit Control Model 08 2005 Information Guide 925 1...
Страница 2: ...ii UDC2500 Universal Digital Limit ControllerProduct Manual 8 05...
Страница 10: ......
Страница 76: ...Input Calibration 66 UDC2500 Universal Digital Limit ControllerProduct Manual 8 05...
Страница 126: ......
Страница 127: ......
Страница 128: ......