Troubleshooting
Algas-SDI Operations & Maintenance Manual P/N 52632
6-45
Liquid Level Switch Tests (P120 through P320)
Disconnect power from the vaporizer at the Main disconnect. Open the control
box and disconnect the two blue wires from terminals P1 and P2 on the control
board. Check for continuity between the two wires as shown below. If your
meter reads 0 ohms, the float switch is good. Recheck vaporizer operation. If
the switch is good and the control board still reads
"4"
, change the control board.
If the switch reads open (OL on the meter) perform the following tests:
Remove the conduit elbow cover at the liquid level switch. Disconnect and
separate the four wires and test as shown below. A reading other than what is
indicated shows a bad liquid level switch. Replace it. If the liquid level switch is
good, repair the wiring between the liquid level switch and the control board.
Figure 22 - Liquid Level Switch Tests P120 - P320
Liquid Level Switch Test.dxf
OHM