Echoflex Installation Guide

Emergency Bypass Load Controller

5. Connect the normal sense wiring leads.

a. Connect the

Normal Power Sense

[Black 1 mm

2

(18 AWG)] and

Normal Switch Sense

[Red 1 mm

2

(18 AWG)] wiring leads to the

normal lighting circuit .

Note:

To ensure that the emergency lighting in the controlled

area turns On in the event of a power loss, you must connect the
Normal Power Sense wires upstream of any switched control
device for the normal lighting loads.

b. Connect the

Normal Neutral

[White 1 mm

2

(18 AWG)] lead to the

normal Neutral for the lighting loads.

6. Are you are installing a remote triggering device to remotely activate

the emergency circuit?

No: Go to

Initial Test on page 8

to confirm the connection.

Yes: See

Remote Activation Input below

for wiring instructions.

7. Replace the cover plate and restore power to the circuits.

Wiring Diagram

Emergency Bypass
Load Controller  EREB-AP

Remote

LED

Option
Button

Status

LED

Emergency Power In (Black 4 mm²)

Emergency Power Out (Red 4 mm²)

Emergency Neutral (Gray 1 mm²)

Normal Power Sense (Black 1 mm²)

Normal Switch Sense (Red 1 mm²)

Normal Neutral (White 1 mm²)

Normally Closed:
-Test Switch
-Fire Alarm Panel
-Security System

Remote Activation Input

The EREB-AP offers a normally closed, dry contact input to accommodate
connection to a fire alarm panel, security system, or test switch. This
input ships from the factory with a blue wire loop (jumper) on the side of
the device. It is a complete loop that disables remote activation. Do not
cut this jumper unless you are installing a remote triggering device.

Note:

Echoflex recommends that you power up and test your

system before connecting to a remote device.

Emergency Bypass Load Controller

Page 4 of 12

Echoflex

Содержание EREB-AP

Страница 1: ...operation The EREB ensures a lights on override by using a normally closed emergency contact closure that interfaces with fire alarm and emergency systems The EREB is available in two models to provi...

Страница 2: ...e c blage du courant alternatif v rifiez que les disjoncteurs pour l alimentation normale et pour l alimentation de secours sont en position d arr t et suivez les proc dures de v rouillage tiquetage p...

Страница 3: ...y to the exterior of the junction box or panel either at the electrical lighting load or before the loads in the circuit See Examples of Use on page 10 Two sets of wire bundles are provided on the top...

Страница 4: ...ow for wiring instructions 7 Replace the cover plate and restore power to the circuits Wiring Diagram Emergency Bypass Load Controller EREB AP Remote LED Option Button Status LED Emergency Power In Bl...

Страница 5: ...ect normal sense and emergency power wires Four screw terminals on the top of the device are used for the following connections The two terminals on the left have a factory installed wire loop jumper...

Страница 6: ...nnect to the terminals labeled 0 10 V FLO See Examples of Use on page 10 for more information 6 Are you are installing a remote triggering device to remotely activate the emergency circuit No Go to In...

Страница 7: ...o your EREB See Initial Test on page 8 2 Remove the wire loop jumper from the Remote Loop In and Remote Loop Out terminals 3 Connect the Remote Loop In and Remote Loop Out terminals on the EREB AD to...

Страница 8: ...ghting is not required 4 Confirm the automatic emergency On functionality by turning Off the circuit breaker in the normal panel The connected emergency lighting should immediately turn On again and t...

Страница 9: ...ntrol circuit thereby illuminating the load and bypassing the normal control signal to the load In a properly operating system the load should illuminate upon pressing the Test button Remote Activatio...

Страница 10: ...Power Sense Black Normal Neutral White Normal Light Fixture Emergency Power Out Red EREB Emerg Light Fixture Switch Backup Arrangement When normal power is present the emergency fixture is turned OFF...

Страница 11: ...ol EREB AD model only When normal power is present and the switch is closed both 0 10 V controlled fixtures dim When normal power is present and the switch is open both 0 10 V controlled fixtures turn...

Страница 12: ...quipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC rules These limits are designed to provide reasonable protection against harmfu...

Отзывы: