Echoflex Installation Guide
Emergency Bypass Load Controller
4. Connect the normal lighting circuit to the
Normal Power Sense
,
Normal Switch Sense
, and
Normal Neutral
screw terminals.
a.
Note:
To ensure that the emergency lighting connected to the
device turns On in the event of a power loss, the Normal Power
Sense wire must be connected upstream of any switched control
device for the normal lighting loads.
5. If you are connecting to 0–10 VDC or fluorescent lighting loads,
connect to the terminals, labeled 0–10 V/ FLO. See
for more information.
6. Are you are installing a remote triggering device to remotely activate
the emergency circuit?
•
No: Go to
to confirm the connection.
•
Yes: See
Remote Activation Input on the facing page
for wiring
instructions.
Wiring Diagram
Normally Closed:
-Test Switch
-Fire Alarm Panel
-Security System
Emergency Power In
Emergency Neutral
Emergency Power Out
Normal Switch Sense
Normal Power Sense
Normal Neutral
EREB-AD
Note:
Screw terminals
accept single wires.
Status
LED
Remote
LED
Option
Button
Remote
Loop
0–10 V/
FLO
Emergency Bypass Load Controller
Page 6 of 12