Echoflex Installation Guide

Emergency Bypass Load Controller

Initial Test

Initial testing of the EREB should be done with the

Remote Loop In

and

Remote Loop Out

jumper installed on the EREB-AD and the blue loop

uncut on the EREB-AP.

1. Turn On the circuit breaker in the emergency panel for the controlled

circuit. The Status LED on the EREB shows red. With only the
emergency circuit On (normal power should be Off), the emergency
lighting should be activated.

2. Temporarily disconnect and cap the wire lead connected to the

Normal Switch Sense

terminal on the EREB. This disables the normal

control function and allows exclusive testing of the emergency On
functionality.

3. Turn On the circuit breaker in the normal panel for the controlled

circuit. The Status LED on the EREB shows green, indicating that
normal power is present and emergency lighting is not required.

4. Confirm the automatic emergency On functionality by turning Off the

circuit breaker in the normal panel. The connected emergency
lighting should immediately turn On again and the Status LED on the
EREB shows red.

5. With the normal circuit breaker secured Off, reconnect the

Normal

Switch Sense

wire to the terminal.

6. Turn On the normal circuit breaker. The EREB should now behave as

described in

Examples of Use on page 10

.

Note:

If you are installing a remote activation input to the EREB,

see

Remote Activation Input on page 4

for the EREB-AP or

Remote

Activation Input on the previous page

for the EREB-AD.

Manual Switch Test

The EREB features a button to manually switch the load from normal to
emergency power for test purposes.

1. Press and hold the red

[Test]

button on the front of the device.

2. Verify the emergency relay closes. This is apparent when the

emergency loads turn on according to your installation.

3. Release the button to return to normal operation.

Emergency Bypass Load Controller

Page 8 of 12

Echoflex

Содержание EREB-AP

Страница 1: ...operation The EREB ensures a lights on override by using a normally closed emergency contact closure that interfaces with fire alarm and emergency systems The EREB is available in two models to provi...

Страница 2: ...e c blage du courant alternatif v rifiez que les disjoncteurs pour l alimentation normale et pour l alimentation de secours sont en position d arr t et suivez les proc dures de v rouillage tiquetage p...

Страница 3: ...y to the exterior of the junction box or panel either at the electrical lighting load or before the loads in the circuit See Examples of Use on page 10 Two sets of wire bundles are provided on the top...

Страница 4: ...ow for wiring instructions 7 Replace the cover plate and restore power to the circuits Wiring Diagram Emergency Bypass Load Controller EREB AP Remote LED Option Button Status LED Emergency Power In Bl...

Страница 5: ...ect normal sense and emergency power wires Four screw terminals on the top of the device are used for the following connections The two terminals on the left have a factory installed wire loop jumper...

Страница 6: ...nnect to the terminals labeled 0 10 V FLO See Examples of Use on page 10 for more information 6 Are you are installing a remote triggering device to remotely activate the emergency circuit No Go to In...

Страница 7: ...o your EREB See Initial Test on page 8 2 Remove the wire loop jumper from the Remote Loop In and Remote Loop Out terminals 3 Connect the Remote Loop In and Remote Loop Out terminals on the EREB AD to...

Страница 8: ...ghting is not required 4 Confirm the automatic emergency On functionality by turning Off the circuit breaker in the normal panel The connected emergency lighting should immediately turn On again and t...

Страница 9: ...ntrol circuit thereby illuminating the load and bypassing the normal control signal to the load In a properly operating system the load should illuminate upon pressing the Test button Remote Activatio...

Страница 10: ...Power Sense Black Normal Neutral White Normal Light Fixture Emergency Power Out Red EREB Emerg Light Fixture Switch Backup Arrangement When normal power is present the emergency fixture is turned OFF...

Страница 11: ...ol EREB AD model only When normal power is present and the switch is closed both 0 10 V controlled fixtures dim When normal power is present and the switch is open both 0 10 V controlled fixtures turn...

Страница 12: ...quipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC rules These limits are designed to provide reasonable protection against harmfu...

Отзывы: