DIP Switch Settings

DIP switches on the sensor electronics provide for additional configuration
options including Use Custom Config, Vacancy Timeout, Enable/Disable
detection LEDs, PIR Only, and the ability to restore the sensor to its factory
defaults.

Switch #

Use

1

Unused

2

Enable/Disable Custom Config Mode

When “Custom Config” is set to Off (also known as Basic
configuration mode), local DIP switch settings for Vacancy
Timeout, Enable PIR LED, and dual technology features are
used. See

Configuration using Elaho Program Mode on

page 1

.

When “Custom Config” is set to On, all other local DIP
switch settings are ignored. Instead, the settings made by
the EchoAccess Mobile App are used.

3 and 4

Vacancy Timeout

5 min = Switches 3 and 4 are Off

15 min = Switch 3 is Off and Switch 4 is On (default)

30 min = Switch 3 is On and Switch 4 is Off

Auto = Both switches are On

5

Detection LEDs

When set to On (default), the occupancy detection LEDs
illuminate when movement is detected.

When set to Off, the occupancy detection LEDs are
disabled unless the unit is in Walk Test mode.

6

PIR Only Mode

When set to On, acoustic detection technology is disabled
for the sensor.

When set to Off (default), both PIR and acoustic detection
technologies are used by the sensor.

7

Unused

8

Restore to Defaults at boot

When set to On, then cycling power to the sensor, the unit
restores to its factory default settings.

Off is the default setting.

Dual Tech Wall-mount Vacancy Sensor

Page 7 of 12

Echoflex Solutions, Inc.

Содержание Elaho Dual Tech Wall-mount Vacancy Sensor

Страница 1: ...y upon detection of vacancy The wall mount unit offers up to 140 degree field of detection with optimized lens options to accommodate wide or narrow angle spaces and is available in white black or cre...

Страница 2: ...ls use only The sensor operates in ambient temperatures of 10 C to 40 C with a maximum of 90 non condensing humidity Installation Echoflex recommends paying special attention to the installation envir...

Страница 3: ...or ESD protection Pull an additional 14 AWG 2 5 mm2 wire for grounding when control wires are not installed in grounded metal conduit Note When using Category 5 or equivalent cable on the EchoConnect...

Страница 4: ...0 mm 2 Connect the EchoConnect pigtail wires from the mounting bracket to the installed wall wires a Connect the data typically black EchoConnect wire from mounting bracket to the incoming EchoConnect...

Страница 5: ...ets engage d If the wall plate does not fully attach wiggle the bottom of the plate until all of the magnets are seated properly a b c d 5 Attach the sensor head a Slide the removable cover off the se...

Страница 6: ...used and have no functionality on the Dual Tech Wall mount Vacancy Sensor Set Space and Address Two rotary switches on the controller provide for assignment of the sensor Space and Address By default...

Страница 7: ...red Instead the settings made by the EchoAccess Mobile App are used 3 and 4 Vacancy Timeout 5 min Switches 3 and 4 are Off 15 min Switch 3 is Off and Switch 4 is On default 30 min Switch 3 is On and S...

Страница 8: ...hen the vacancy timeout in the space has only been reset by acoustic detection for 60 minutes acoustic detection is disabled until the next PIR detection event PIR only Detection When acoustic detecti...

Страница 9: ...he sensor does not detect occupancy again during the vacancy timeout period the lights turn off and a 30 second grace period begins Grace Period The sensor features a 30 second grace period after a va...

Страница 10: ...f the sensor to enable the Walk Test feature A green LED will flash indicating Walk Test is enabled and the vacancy timer will be shortened to ten seconds 3 Move throughout the space including corners...

Страница 11: ...or Sensor Coverage Narrow Lens 100ft 30 5m 18 3m 60ft 2 2m 7ft 1m 3ft 2 1m 6 8ft 3m 10ft 10 7m 35ft 6 56 2 5m 8ft 0 C L 77 29 21 5 14 5m 16ft 5m 16ft 2 5m 8ft Top View Side View Dual Tech Wall mount V...

Страница 12: ...e Dual Tech Vacancy Sensor Wide Lens 19 4 0 5m 10m 16ft 33ft 5m 10m 16ft 33ft 15 3m 7 7 m 4 6m 1 7m 50ft 25ft 15ft 6ft 2 1m 6 8ft 140 Top View Side View Dual Tech Wall mount Vacancy Sensor Page 12 of...

Отзывы: