Echoflex Installation Guide

Dual Tech Vacancy Sensor

Walk Test

The sensor offers a Walk Test mode, which shortens the vacancy timer to ten
seconds and allows for simple and quick verification of the sensor’s coverage
and range in the installed space.

[Walk Test] 
button

1.

Prepare the site for configuration.

a.

Make certain the sensor and lighting loads are powered and
connected for control by the Elaho control system.

b.

You will need direct access to the sensor in order to place it into
Walk Test mode.

2.

Press the

[Walk Test]

button on the bottom of the sensor to enable

the Walk Test feature. A green LED will flash, indicating Walk Test is
enabled and the vacancy timer will be shortened to ten seconds.

3.

Move throughout the space including corners and areas that may be
obscured from line of sight to the sensor. Each time the sensor detects
movement, the lens illuminates red. If acoustic detection is enabled,
any sound detected will illuminate the lens green.

4.

As needed, adjust the angle of the sensor head to obtain optimal
detection in the space.

5.

Walk Test mode automatically exits and the sensor returns to normal
operation after five minutes. You can also manually terminate by
pressing the

[Walk Test]

button again.

Dual Tech Wall-mount Vacancy Sensor

Page 10 of 12

Echoflex Solutions, Inc.

Содержание Elaho Dual Tech Wall-mount Vacancy Sensor

Страница 1: ...y upon detection of vacancy The wall mount unit offers up to 140 degree field of detection with optimized lens options to accommodate wide or narrow angle spaces and is available in white black or cre...

Страница 2: ...ls use only The sensor operates in ambient temperatures of 10 C to 40 C with a maximum of 90 non condensing humidity Installation Echoflex recommends paying special attention to the installation envir...

Страница 3: ...or ESD protection Pull an additional 14 AWG 2 5 mm2 wire for grounding when control wires are not installed in grounded metal conduit Note When using Category 5 or equivalent cable on the EchoConnect...

Страница 4: ...0 mm 2 Connect the EchoConnect pigtail wires from the mounting bracket to the installed wall wires a Connect the data typically black EchoConnect wire from mounting bracket to the incoming EchoConnect...

Страница 5: ...ets engage d If the wall plate does not fully attach wiggle the bottom of the plate until all of the magnets are seated properly a b c d 5 Attach the sensor head a Slide the removable cover off the se...

Страница 6: ...used and have no functionality on the Dual Tech Wall mount Vacancy Sensor Set Space and Address Two rotary switches on the controller provide for assignment of the sensor Space and Address By default...

Страница 7: ...red Instead the settings made by the EchoAccess Mobile App are used 3 and 4 Vacancy Timeout 5 min Switches 3 and 4 are Off 15 min Switch 3 is Off and Switch 4 is On default 30 min Switch 3 is On and S...

Страница 8: ...hen the vacancy timeout in the space has only been reset by acoustic detection for 60 minutes acoustic detection is disabled until the next PIR detection event PIR only Detection When acoustic detecti...

Страница 9: ...he sensor does not detect occupancy again during the vacancy timeout period the lights turn off and a 30 second grace period begins Grace Period The sensor features a 30 second grace period after a va...

Страница 10: ...f the sensor to enable the Walk Test feature A green LED will flash indicating Walk Test is enabled and the vacancy timer will be shortened to ten seconds 3 Move throughout the space including corners...

Страница 11: ...or Sensor Coverage Narrow Lens 100ft 30 5m 18 3m 60ft 2 2m 7ft 1m 3ft 2 1m 6 8ft 3m 10ft 10 7m 35ft 6 56 2 5m 8ft 0 C L 77 29 21 5 14 5m 16ft 5m 16ft 2 5m 8ft Top View Side View Dual Tech Wall mount V...

Страница 12: ...e Dual Tech Vacancy Sensor Wide Lens 19 4 0 5m 10m 16ft 33ft 5m 10m 16ft 33ft 15 3m 7 7 m 4 6m 1 7m 50ft 25ft 15ft 6ft 2 1m 6 8ft 140 Top View Side View Dual Tech Wall mount Vacancy Sensor Page 12 of...

Отзывы: