Echoflex Installation Guide

Dual Tech Vacancy Sensor

Installation

Note:

Follow all local code requirements for terminating wire.

The wall-mount sensor is provided with a mounting bracket with pre-routed
wires that can be mounted to a back box. Follow the detailed instructions for
installation.

1.

Pull the Belden 8471 (or equivalent) and one 14 AWG (2.5 mm

2

) ground

wire to the mounting location (switch box or surface) and strip each
wire 3/8” (9–10 mm).

2.

Connect the EchoConnect pigtail wires from the mounting bracket to
the installed wall wires.

a.

Connect the data - (typically black) EchoConnect wire from
mounting bracket to the incoming EchoConnect (typically black)
wire using a WAGO wire termination connector.

b.

Repeat the above steps for the data + (typically white)
EchoConnect wire and for the ESD ground wire, using a new
WAGO connector for each termination type.

3.

Orient the mounting plate, with the directional arrows in the upright
position, to the mounting box and secure it in place using the two
screws provided.

Dual Tech Wall-mount Vacancy Sensor

Page 4 of 12

Echoflex Solutions, Inc.

Содержание Elaho Dual Tech Wall-mount Vacancy Sensor

Страница 1: ...y upon detection of vacancy The wall mount unit offers up to 140 degree field of detection with optimized lens options to accommodate wide or narrow angle spaces and is available in white black or cre...

Страница 2: ...ls use only The sensor operates in ambient temperatures of 10 C to 40 C with a maximum of 90 non condensing humidity Installation Echoflex recommends paying special attention to the installation envir...

Страница 3: ...or ESD protection Pull an additional 14 AWG 2 5 mm2 wire for grounding when control wires are not installed in grounded metal conduit Note When using Category 5 or equivalent cable on the EchoConnect...

Страница 4: ...0 mm 2 Connect the EchoConnect pigtail wires from the mounting bracket to the installed wall wires a Connect the data typically black EchoConnect wire from mounting bracket to the incoming EchoConnect...

Страница 5: ...ets engage d If the wall plate does not fully attach wiggle the bottom of the plate until all of the magnets are seated properly a b c d 5 Attach the sensor head a Slide the removable cover off the se...

Страница 6: ...used and have no functionality on the Dual Tech Wall mount Vacancy Sensor Set Space and Address Two rotary switches on the controller provide for assignment of the sensor Space and Address By default...

Страница 7: ...red Instead the settings made by the EchoAccess Mobile App are used 3 and 4 Vacancy Timeout 5 min Switches 3 and 4 are Off 15 min Switch 3 is Off and Switch 4 is On default 30 min Switch 3 is On and S...

Страница 8: ...hen the vacancy timeout in the space has only been reset by acoustic detection for 60 minutes acoustic detection is disabled until the next PIR detection event PIR only Detection When acoustic detecti...

Страница 9: ...he sensor does not detect occupancy again during the vacancy timeout period the lights turn off and a 30 second grace period begins Grace Period The sensor features a 30 second grace period after a va...

Страница 10: ...f the sensor to enable the Walk Test feature A green LED will flash indicating Walk Test is enabled and the vacancy timer will be shortened to ten seconds 3 Move throughout the space including corners...

Страница 11: ...or Sensor Coverage Narrow Lens 100ft 30 5m 18 3m 60ft 2 2m 7ft 1m 3ft 2 1m 6 8ft 3m 10ft 10 7m 35ft 6 56 2 5m 8ft 0 C L 77 29 21 5 14 5m 16ft 5m 16ft 2 5m 8ft Top View Side View Dual Tech Wall mount V...

Страница 12: ...e Dual Tech Vacancy Sensor Wide Lens 19 4 0 5m 10m 16ft 33ft 5m 10m 16ft 33ft 15 3m 7 7 m 4 6m 1 7m 50ft 25ft 15ft 6ft 2 1m 6 8ft 140 Top View Side View Dual Tech Wall mount Vacancy Sensor Page 12 of...

Отзывы: