Echoflex Installation Guide

Dual Tech Ceiling-mount Vacancy Sensor

Control Wire Specification

The sensor connects to the EchoConnect

®

communication bus. EchoConnect is

a bidirectional protocol that uses one pair of wires (data + and data -) for both
data and power. Echoflex recommends using Belden 8471 (or approved equal)
Class 2 wire. The total combined length of an EchoConnect wire run (using
Belden 8471, or equal) may not exceed 1,640 feet (500 m).

Note:

All control wiring should be installed and terminated by a

qualified installer and should follow standard wiring installation practices.

Leave approximately 8" (20 cm) of wiring in the back box for connection
and to allow slack for future service needs.

Note:

Echoflex requires that all Elaho stations and devices be grounded

for ESD protection. Pull an additional 14 AWG (2.5 mm

2

) wire for

grounding when control wires are not installed in grounded metal conduit.

Note:

When using Category 5 (or equivalent) cable on the EchoConnect

communication bus, please note the following:

Cat5 wiring must be terminated using EchoConnect Cat5
Termination Kit and must be installed using a bus topology.
Refer to the installation guide that is provided with the Cat5
Termination Kit (8186A1207) for information to terminate
Cat5 wiring.

Not all topologies are supported using Cat5; careful planning
is required to ensure the proper termination kits are available
and the wire is pulled appropriately.

Parts and Supplies

The following parts and supplies are included with the sensor:

soft ceiling tile adapters

2 each screws, 6-32 x 3/4” and 1 3/4”

lens masks

WAGO connectors (wire termination connectors)

Dual Tech Ceiling-mount Vacancy Sensor

Page 3 of 12

Echoflex Solutions, Inc.

Содержание Elaho Dual Tech Ceiling-mount Vacancy Sensor

Страница 1: ...tionality upon detection of vacancy The ceiling mount sensor offers 360 degree coverage with optimized lens options to accommodate small and large spaces The sensor is available in a white or black fi...

Страница 2: ...al attention to the installation environment When operating in PIR only modes the sensor must have an unobstructed view of the room Do not mount behind or near tall cabinets shelves hanging light fixt...

Страница 3: ...devices be grounded for ESD protection Pull an additional 14 AWG 2 5 mm2 wire for grounding when control wires are not installed in grounded metal conduit Note When using Category 5 or equivalent cabl...

Страница 4: ...location junction box or finished surface and strip each wire 3 8 9 10 mm 2 Temporarily remove the sensor cover to gain access to the configuration switches and mounting access holes Hold the sensor i...

Страница 5: ...hole for wire pass through b Remove the ceiling tile material from marked access hole c Pull the sensor wires through the access hole 4 Insert the soft ceiling tile adapters through the provided pinho...

Страница 6: ...nctionality on the Dual Tech Ceiling mount Vacancy Sensor DIP switches Space and Address switches Set Space and Address Two rotary switches on the controller provide for assignment of the sensor Space...

Страница 7: ...e ignored Instead the settings made by the EchoAccess Mobile App are used 3 and 4 Vacancy Timeout 5 min Switches 3 and 4 are Off 15 min Switch 3 is Off and Switch 4 is On default 30 min Switch 3 is On...

Страница 8: ...eout When the vacancy timeout in the space has only been reset by acoustic detection for 60 minutes acoustic detection is disabled until the next PIR detection event PIR only Detection When acoustic d...

Страница 9: ...s If the sensor does not detect occupancy again during the vacancy timeout period the lights turn off and a 30 second grace period begins Grace Period The sensor features a 30 second grace period afte...

Страница 10: ...seconds 3 Move throughout the space including corners and areas that may be obscured from line of sight to the sensor Each time the sensor detects movement the lens illuminates red If acoustic detect...

Страница 11: ...10 ft 3 0 m 10 ft 4 6 m 15 ft 4 6 m 15 ft 6 1 m 20 ft 6 1 m 20 ft 8 ft 2 4 m 10 ft 3 0 m 12 ft 3 7 m Large Room Lens Side View 0 8 ft 2 4 m 10 ft 3 0 m 12 ft 3 7 m 0 3 0 m 10 ft 3 0 m 10 ft 6 1 m 20...

Страница 12: ...Echoflex Installation Guide Dual Tech Ceiling mount Vacancy Sensor Dual Tech Ceiling mount Vacancy Sensor Page 12 of 12 Echoflex Solutions Inc...

Отзывы: