background image

Echoflex Installation Guide

Dual Tech Ceiling-mount Vacancy Sensor

Sensor Configuration

The Elaho Dual Tech Ceiling-mount Vacancy Sensor participates in an
Elaho control system using the configured Space and Address, which are
selectable using the rotary switches on the sensor electronics located behind
the removable cover.

DIP switches, also located on the sensor electronics, set the sensor
functionality.

Note:

The

[MODE] and [AUX] buttons, and their related LEDs, are not

used and have no functionality on the Dual Tech Ceiling-mount Vacancy
Sensor.

DIP switches

Space and Address 
switches

Set Space and Address

Two rotary switches on the controller provide for assignment of the sensor
Space and Address. By default, these switches are set to Space 1, Address 1.
Commands are shared by all devices within a given space.

1.

Set the Space rotary switch to the desired number (1 through 16) for
the space you want the sensor to control.

2.

Set the Address rotary switch to desired address (1 through 16) for the
sensor identification in the selected space.

Note:

Do not duplicate a device Address within the same Space.

Dual Tech Ceiling-mount Vacancy Sensor

Page 6 of 12

Echoflex Solutions, Inc.

Содержание Elaho Dual Tech Ceiling-mount Vacancy Sensor

Страница 1: ...tionality upon detection of vacancy The ceiling mount sensor offers 360 degree coverage with optimized lens options to accommodate small and large spaces The sensor is available in a white or black fi...

Страница 2: ...al attention to the installation environment When operating in PIR only modes the sensor must have an unobstructed view of the room Do not mount behind or near tall cabinets shelves hanging light fixt...

Страница 3: ...devices be grounded for ESD protection Pull an additional 14 AWG 2 5 mm2 wire for grounding when control wires are not installed in grounded metal conduit Note When using Category 5 or equivalent cabl...

Страница 4: ...location junction box or finished surface and strip each wire 3 8 9 10 mm 2 Temporarily remove the sensor cover to gain access to the configuration switches and mounting access holes Hold the sensor i...

Страница 5: ...hole for wire pass through b Remove the ceiling tile material from marked access hole c Pull the sensor wires through the access hole 4 Insert the soft ceiling tile adapters through the provided pinho...

Страница 6: ...nctionality on the Dual Tech Ceiling mount Vacancy Sensor DIP switches Space and Address switches Set Space and Address Two rotary switches on the controller provide for assignment of the sensor Space...

Страница 7: ...e ignored Instead the settings made by the EchoAccess Mobile App are used 3 and 4 Vacancy Timeout 5 min Switches 3 and 4 are Off 15 min Switch 3 is Off and Switch 4 is On default 30 min Switch 3 is On...

Страница 8: ...eout When the vacancy timeout in the space has only been reset by acoustic detection for 60 minutes acoustic detection is disabled until the next PIR detection event PIR only Detection When acoustic d...

Страница 9: ...s If the sensor does not detect occupancy again during the vacancy timeout period the lights turn off and a 30 second grace period begins Grace Period The sensor features a 30 second grace period afte...

Страница 10: ...seconds 3 Move throughout the space including corners and areas that may be obscured from line of sight to the sensor Each time the sensor detects movement the lens illuminates red If acoustic detect...

Страница 11: ...10 ft 3 0 m 10 ft 4 6 m 15 ft 4 6 m 15 ft 6 1 m 20 ft 6 1 m 20 ft 8 ft 2 4 m 10 ft 3 0 m 12 ft 3 7 m Large Room Lens Side View 0 8 ft 2 4 m 10 ft 3 0 m 12 ft 3 7 m 0 3 0 m 10 ft 3 0 m 10 ft 6 1 m 20...

Страница 12: ...Echoflex Installation Guide Dual Tech Ceiling mount Vacancy Sensor Dual Tech Ceiling mount Vacancy Sensor Page 12 of 12 Echoflex Solutions Inc...

Отзывы: