Echoflex Installation Guide

Dual Tech Ceiling-mount Vacancy Sensor

Power Up and Test

Power Up

All EchoConnect terminations in the system must be made before applying
power to the system and sensor. When the sensor is powered up, the PIR and
acoustic detection LEDs illuminate for one minute for calibration and warm-
up, then return to normal operation according to the configuration.

Both the PIR and acoustic detection features of the sensor will automatically
adjust sensitivity threshold to eliminate nuisance tripping. During this time,
sensor configuration is not allowed and no events are triggered.

Dual Technology

When both PIR and acoustic detection are used, the following logic is used:

When the space is vacant, only manual control can switch the state to
occupied.

When the space is occupied, PIR, acoustic detection, and manual
control can reset the vacancy timeout.

When the vacancy timeout in the space has only been reset by acoustic
detection for 60 minutes, acoustic detection is disabled until the next
PIR detection event.

PIR (only) Detection

When acoustic detection is disabled (DIP switch 6 set to On), the following
logic is used:

When the space is vacant, only manual control can switch the state to
occupied.

When the space is occupied, PIR detection and manual control can
reset the vacancy timeout.

Basic Configuration

When the sensor is in Basic configuration mode (DIP switch 2 set to Off), the
sensor will activate a Space Off command when vacancy is detected.

Custom Configuration Mode

When functionality other than Space Off is required, place the sensor in
Custom configuration mode (DIP switch 2 set to On). Customization of the
sensor and all actions are configured using the ElahoAccess Mobile App.

For more detailed information about custom configuration options available
using ElahoAccess, see the ElahoAccess Mobile App integrated help system.

Dual Tech Ceiling-mount Vacancy Sensor

Page 8 of 12

Echoflex Solutions, Inc.

Содержание Elaho Dual Tech Ceiling-mount Vacancy Sensor

Страница 1: ...tionality upon detection of vacancy The ceiling mount sensor offers 360 degree coverage with optimized lens options to accommodate small and large spaces The sensor is available in a white or black fi...

Страница 2: ...al attention to the installation environment When operating in PIR only modes the sensor must have an unobstructed view of the room Do not mount behind or near tall cabinets shelves hanging light fixt...

Страница 3: ...devices be grounded for ESD protection Pull an additional 14 AWG 2 5 mm2 wire for grounding when control wires are not installed in grounded metal conduit Note When using Category 5 or equivalent cabl...

Страница 4: ...location junction box or finished surface and strip each wire 3 8 9 10 mm 2 Temporarily remove the sensor cover to gain access to the configuration switches and mounting access holes Hold the sensor i...

Страница 5: ...hole for wire pass through b Remove the ceiling tile material from marked access hole c Pull the sensor wires through the access hole 4 Insert the soft ceiling tile adapters through the provided pinho...

Страница 6: ...nctionality on the Dual Tech Ceiling mount Vacancy Sensor DIP switches Space and Address switches Set Space and Address Two rotary switches on the controller provide for assignment of the sensor Space...

Страница 7: ...e ignored Instead the settings made by the EchoAccess Mobile App are used 3 and 4 Vacancy Timeout 5 min Switches 3 and 4 are Off 15 min Switch 3 is Off and Switch 4 is On default 30 min Switch 3 is On...

Страница 8: ...eout When the vacancy timeout in the space has only been reset by acoustic detection for 60 minutes acoustic detection is disabled until the next PIR detection event PIR only Detection When acoustic d...

Страница 9: ...s If the sensor does not detect occupancy again during the vacancy timeout period the lights turn off and a 30 second grace period begins Grace Period The sensor features a 30 second grace period afte...

Страница 10: ...seconds 3 Move throughout the space including corners and areas that may be obscured from line of sight to the sensor Each time the sensor detects movement the lens illuminates red If acoustic detect...

Страница 11: ...10 ft 3 0 m 10 ft 4 6 m 15 ft 4 6 m 15 ft 6 1 m 20 ft 6 1 m 20 ft 8 ft 2 4 m 10 ft 3 0 m 12 ft 3 7 m Large Room Lens Side View 0 8 ft 2 4 m 10 ft 3 0 m 12 ft 3 7 m 0 3 0 m 10 ft 3 0 m 10 ft 6 1 m 20...

Страница 12: ...Echoflex Installation Guide Dual Tech Ceiling mount Vacancy Sensor Dual Tech Ceiling mount Vacancy Sensor Page 12 of 12 Echoflex Solutions Inc...