26/37
Item no.: HAB 100177146 - 000 · EN · Change ·Release 2020-10-26
Control electronics
Control electronics
VTD-60.XX-K5SB
VTD-60.XX-K5SB
Installation
Connection of the screw terminals Weidmueller BVZ 7.62 HP
(installed in VTD-60.35-K5SB – interface X1)
The drive controllers use connectors with screw technology for the output side
The following overview shows which conductor cross-sections can be used with the connector:
Terminal Designation/item no.
Terminal area (cross-section d) mm
2
Stripping
length mm
Single-wire
H05(07)V-U
Fine-wire
H05(07)V-K
Fine-wire
with wire-end
ferrule
Fine wire with
wire-end
ferrule and
plastic collar
X1
BLZ 7.62HP/06 1929970000
0.2 to 6
0.5 to 6
0.25 to 6
0.25 to 6
12
Connection of the tension spring terminals Weidmueller B2CF 3.5
(interface X2, X3, X4)
The drive controllers use connectors with tension spring technology for single/fine-wire conductors
The following overview shows which conductor cross-sections can be used with the connector:
Terminal Designation/item no.
Terminal area (cross-section d) mm
2
Stripping
length mm
Single-wire
H05(07)V-U
Fine-wire
H05(07)V-K
Fine-wire
with wire-end
ferrule
Fine wire with
wire-end
ferrule and
plastic collar
X2
B2CF 3.5/14 1277520000
0.14 to 1.5
0.14 to 1.5
0.14 to 1.5
0.14 to 1
10
X3
B2CF 3.5/12 1277510000
X4
B2CF 3.5/6 1277470000
Screwdriver
Insulation
Single/fine-wire conductor
Conductor with wire-end ferrule
d = core cross-section
Insulation
d
Screwdriver
Insulation
Insulation
Single/fine-wire conductor
Conductor with wire-end
ferrule
d
d = core cross-section