28
XSTORAGE HOME 3P USER MANUAL
MN700011EN December 2020 www.eaton.com
E003
TYPE
SOLUTION
E011
High grid voltage
Make sure that the grid voltage is within the range allowed by
local regulations.
Contact the grid operator to evaluate the possibility of adapting
the voltages at the connection point or request approval for the
change to the operating limits.
If the grid voltage is within the allowed range, but the alarm
persists, please contact Eaton technical support representative.
E012
High grid voltage
Make sure that the grid voltage is within the range allowed by
local regulations.
Contact the grid operator to evaluate the possibility of adapting
the voltages at the connection point or request approval for the
change to the operating limits.
If the grid voltage is within the allowed range, but the alarm
persists, please contact Eaton technical support representative.
E013
Low grid voltage
Make sure that the grid voltage is within the range allowed by
local regulations.
Contact the grid operator to evaluate the possibility of adapting
the voltages at the connection point or request approval for the
change to the operating limits.
If the grid voltage is within the allowed range, but the alarm
persists, please contact Eaton technical support representative.
E014
Low grid voltage
Make sure that the grid voltage is within the range allowed by
local regulations.
Contact the grid operator to evaluate the possibility of adapting
the voltages at the connection point or request approval for the
change to the operating limits.
If the grid voltage is within the allowed range, but the alarm
persists, please contact Eaton technical support representative.
E015
High grid frequency
Make sure that the grid frequency is within the range allowed
by local regulations.
Contact the grid operator to request approval for the change to
the operating limits.
If the grid frequency is within the allowed range, but the alarm
persists, please contact Eaton technical support representative.
E016
High grid frequency
Make sure that the grid frequency is within the range allowed
by local regulations.
Contact the grid operator to request approval for the change to
the operating limits.
If the grid frequency is within the allowed range, but the alarm
persists, please contact Eaton technical support representative.
E017
High grid frequency
Make sure that the grid frequency is within the range allowed
by local regulations.
Contact the grid operator to request approval for the change to
the operating limits.
If the grid frequency is within the allowed range, but the alarm
persists, please contact Eaton technical support representative.
E018
Low grid frequency
Make sure that the grid frequency is within the range allowed
by local regulations.
Contact the grid operator to request approval for the change to
the operating limits.
If the grid frequency is within the allowed range, but the alarm
persists, please contact Eaton technical support representative.