16
EATON XSTORAGE COMPACT INSTALLATION MANUAL
P-164000907 - March 2022 www.eaton.com
00 Title
Table 3 . Location and environmental requirements
Table 4 . Initial system heat dissipation at nominal power
Requirement
Value
Ambient temperature range
From 0 °C to 35 °C
Recommended operating range
From 20 °C to 25 °C
Maximum relative humidity
95 %, non-condensing
Maximum altitude
2,000 m
For ventilation requirements, see xStorage Compact heat rejection in
Table 4: Initial system heat dissipation at nominal power.
Batteries
Heat rejection (kW)
Type
Quantity
xStorage Compact 20 kW
xStorage Compact 40 kW
GEN 1 (2
nd
life)
21 kWh/string
1 string
1.9
N/A
2 strings
1.6
3.7
3 strings
1.6
3.4
GEN 4
50 kWh/string
1 string
1.6
3.7
2 strings
1.5
3.2
3 strings
1.5
3.1
4.2 Dimensions
Figure 9 . Eaton xStorage Compact system and external battery rack dimensions in mm and inches
1000 mm
(39.4 inches)
19
87 m
m
(7
8.
2 in
ch
es
)
19
87 m
m
(7
8.
2 in
ch
es
)
1000 mm
(39.4 inches)
600 mm
(23.6 inches)
A
B
600 mm
(23.6 inches)