background image

1

Xenon beacon - XB10

English

Xenon beacon - Xb10

   TM102.L   May 2022   www.eaton.com

1.0 Introduction

These compact and lightweight 10 & 15 joule beacons 

have been designed for use in potentially explosive 

atmospheres and harsh environmental conditions. 

The beacon housing, including the flamepaths, is 

manufactured completely from a UV stable glass 

reinforced polyester which is ideally suited for use 

offshore and onshore, where light weight combined with 

corrosion resistance is required.
Stainless steel screws and mounting bracket are 

incorporated ensuring a totally corrosion free unit. 

An additional body clamp is available for high 

vibration environments.

2.0 Installation

General

When installing and operating explosion-protected 

equipment, requirements for selection, installation 

and operation should be referred to e.g. IEE Wiring 

Regulations and the ‘National Electrical Code’ in North 

America. Additional national and/or local requirements 

may apply.
Ensure that all nuts, bolts and fixings are secure.
Ensure that only the correct listed or certified stopping 

plugs are used to blank off unused gland entry points and 

that the NEMA/IP rating of the unit is maintained. MEDC 

recommend the use of a sealing compound such as 

HYLOMAR PL32 on the threads of glands and stopping 

plugs in order to maintain the IP rating of the unit.
The beacon is mounted via the 3 off Ø9mm mounting 

holes in the standard L-shaped bracket fixed to the base of 

the unit. The holes have been designed to accept an M8 

screw or bolt.
MEDC recommend the use of stainless steel fixings.
Note that if the beacon is to be used in high amplitude 

vibration applications, a secondary restraint would be 

advisable. Please contact MEDC for details.

Cable termination

CAUTION: Before removing the cover assembly, 

ensure that the power to the unit is isolated.

General

Cable termination should be in accordance with 

specifications applying to the required application. MEDC 

recommends that all cables and cores should be correctly 

identified. Please refer to the wiring diagram provided 

with the product.
Ensure that only the correct listed or certified cable 

glands are used and that the assembly is shrouded and 

correctly earthed.
All cable glands should be of an equivalent NEMA/IP 

rating to that of the beacon and integrated with the unit 

such that this rating is maintained.

The internal earth terminal, where fitted, must be used 

for the equipment grounding connection and the external 

terminal is for a supplementary bonding connection 

where local codes or authorities permit or require such 

a connection.
Ensure there is not too much slack of cable cores within 

the unit due to space limitations.

Exd unit

Unscrew the set screw in the cover assembly one full 

turn (2.0mm A/F hexagon key). Carefully unscrew and 

remove the cover assembly (using a 120mm hook wrench 

if required). Once the cover assembly has been removed, 

slide the PCB assembly out of the unit until the terminals 

clear the enclosure body.
After cable termination has been completed, the PCB can 

be fully inserted into the enclosure, ensuring the spacer 

on the bottom of the PCB snaps into the retaining clip on 

the boss inside the enclosure base. Be aware of correct 

PCB orientation, illustrated by the label adhered to the 

inside wall of the enclosure body.
To replace the cover, use the same procedure as above 

but in reverse manner, ensuring the O-ring is in good 

condition and fitted in the correct location at the top of 

the cover threads. Ensure the cover is screwed down 

tightly and that there is no damage to the thread surfaces 

or mating faces of the cover and enclosure. There should 

be a maximum gap of 0.2mm between the faces of the 

cover and enclosure to ensure correct o-ring compression.

Exde unit

Unscrew and remove the 2 off M5 screws (4.0mm A/F 

hexagon key) and lift the Exe cover away from the base of 

the unit.
Terminate the field wiring as shown on the wiring diagram 

supplied with the unit.
Not more than one single or multiple strand lead shall be 

connected into either side of any terminal, unless multiple 

conductors have been joined in a suitable manner, e.g. 

two conductors into a single insulated crimped boot 

lace ferrule.
Leads connected to the terminals shall be insulated for 

the appropriate voltage and this insulation shall extend to 

within 1mm of the metal of the terminal throat.
All terminal screws, used and unused, shall be tightened 

down to between 0.5Nm and 0.6Nm. Conductive 

metalwork (inc. cable glands) must be a minimum of 

5mm away from the terminals After cable termination 

has been completed, replace the Exe cover onto the 

enclosure, ensuring there is no damage to the mating 

faces and that the O-ring is correctly seated in its groove 

to maintain the IP rating of the unit. Replace and tighten 

the 2 off M5 cover screws (4.0mm A/F hexagon key). 

DO NOT over tighten the cover screws as this may cause 

damage to the unit.
To maintain the IP rating of the unit, the recommended 

torque on the cover screws is between 2.5 – 3.0Nm.

Содержание XB10

Страница 1: ...Technical manual Xenon beacon XB10...

Страница 2: ...URPOSE OR MERCHANTABILITY OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTENTS OF THIS DOCUMENT SHALL...

Страница 3: ...CTION 1 2 0 INSTALLATION 1 General 1 Cable termination 1 General 1 Exd unit 1 Exde unit 1 3 0 OPERATION 2 4 0 MAINTENANCE 2 Removing replacing xenon tube 2 5 0 CERTIFICATION APPROVALS 3 lECEx units 3...

Страница 4: ...iv Xenon beacon XB10 TM102 L May 2022 www eaton com...

Страница 5: ...for the equipment grounding connection and the external terminal is for a supplementary bonding connection where local codes or authorities permit or require such a connection Ensure there is not too...

Страница 6: ...he unit can be repaired by MEDC All parts of the unit are replaceable If you acquired a significant quantity of units then it is recommended that spares are also made available Please discuss your req...

Страница 7: ...le entry device unused with this apparatus must exceed 12mm in length II Painting and surface finishes other than those applied by the manufacturer are not permitted B Exde units Certificates BAS00ATE...

Страница 8: ...ralit s 5 Connexion des c bles 5 G n ralit s 5 Unit Exd 5 Unit Ex de 5 3 0 FONCTIONNEMENT 6 4 0 MAINTENANCE 6 Retirer remplacer le tube x non 6 5 0 CERTIFICATION HOMOLOGATIONS 7 Unit s IECEx 7 Unit s...

Страница 9: ...P quivalent celui du feu et tre int gr s l unit de fa on assurer le maintien de sa classification La borne interne de mise la terre doit tre utilis e pour mettre l quipement la terre La borne externe...

Страница 10: ...l quipement celui ci peut tre r par par MEDC Toutes les pi ces sont rempla ables Lorsqu un nombre significatif d unit s ont t acquises il est recommand de disposer d unit s de rechange Les technico c...

Страница 11: ...s BAS00ATEX2204X IECEx BAS 10 0086X I Le filtetage de contact de tout p riph rique d entr e de c ble inutilis avec cette appareil doit mesurer plus de 12mm II Toutes peintures ou finitions de surface...

Страница 12: ...llgemeines 9 Kabelenden 9 Allgemeines 9 Exd ger t 9 Exde ger t 9 3 0 BETRIEB 10 4 0 WARTUNG 10 Entfernung Erneuerung der Xenon R hren 10 5 0 ZERTIFIZIERUNG GENEHMIGUNGEN 11 Iecex einheiten 11 ATEX Ein...

Страница 13: ...endet werden und dass die Baugruppe korrekt verkleidet und geerdet ist Alle Kabeldurchf hrungen m ssen ber eine NEMA IP Einstufung verf gen die der des Blinklichts entspricht und in die Einheit integr...

Страница 14: ...kaum oder gar keine Wartung Glasfaserverst rkter Kunststoff h lt den Angriffen der meisten S uren Alkalien und Chemikalien stand und ist wie die meisten Metalle widerstandsf hig gegen ber konzentriert...

Страница 15: ...ild sind mit der ATEX Gruppe und der Kategorie Kennzeichnung versehen II 2 G Hierbei gilt Steht f r die ATEX Kompatibilit t II Steht f r die Eignung in Oberfl chenbranchen 2 Steht f r die Eignung in e...

Страница 16: ...ontained in this document and to prices are reserved so are errors and omissions Only order confirmations and technical documentation by Eaton is binding Photos and pictures also do not warrant a spec...

Отзывы: