SVPD Programming Guide

www.eaton.com/lightingsystems

Lights will not remain ON

occupancy sensitivity may be set to LO

•  Verify that the sensor’s red LED flashes with motion activity.
•  Using the programming remote (ISHH-01) ensure the relay can be turned 

ON/OFF.

•  Using the programming remote (ISHH-01) push the “HI” button to ensure 

occupancy coverage area is maximized.

daylight switching may be enabled in error

•  Using the programming remote (ISHH-01) ensure the relay can be turned 

ON/OFF.

•  Follow the steps in this document ensure that daylight switching is 

disabled.

Lights will not turn OFF 

automatically

occupancy placement or sensitivity

•  Using the programming remote (ISHH-01) ensure the relay can be turned 

ON/OFF.

•  Verify that the sensor’s red LED flashes with motion activity and stops 

flashing with no motion.

•  If the LED flashes when motion is not occurring, ensure the sensor is not 

located within 4-6 feet of air vents.

•  If the LED is flashing when motion is not occurring, using the 

programming remote (ISHH-01) push the “LO” button to reduce 

occupancy coverage area.

unoccupied scene set to ON in error

•  Using the programming remote (ISHH-01) ensure the relay can be turned 

ON/OFF.

•  If the load turns ON with the remote, follow the steps in this document to 

set the unoccupied scene level.

Lights turn ON but remain 

at a dimmed level

0-10V output

•  Using the programming remote (ISHH-01) ensure the relay can be turned 

ON/OFF and the light level can be raised and lowered.

•  If still not responsive, disconnect the 0-10V wires from the control 

module. If the lighting does not go to full bright check wiring for shorts.

•  Verify with a meter that at least 10VDC is present between the purple 

and gray disconnected driver leads.

•  If the lighting does go full bright when disconnected from the control 

module, check for polarity reversal on the 0-10V leads.

daylight dimming is enabled where not 

appropriate

AND/OR

occupancy detection scene level set too low

•  Using the programming remote (ISHH-01) ensure the relay can be turned 

ON/OFF and the light level can be raised and lowered.

•  If the load turns ON and responds to the raise/lower commands, 

determine whether the fixture should dim with daylighting. If it should 

not, follow the steps in this document to disable daylight dimming and 

then set the occupancy detection scene level.

•  If the load should dim with daylighting, it may need recalibration. Follow 

the steps in this document to set the occupancy detection scene level.

Lights turn ON but remain 

at full bright level

0-10V output

•  Using the programming remote (ISHH-01) ensure the relay can be turned 

ON/OFF and the light level can be raised and lowered.

•  If still not responsive, disconnect the 0-10V wires from the control 

module. Lighting should remain full bright.

•  Temporarily connect the driver’s purple and gray wires together. Verify 

the lighting goes full dim.

•  Verify with a meter that at least 10VDC is present between the purple 

and gray disconnected driver leads.

•  If the lighting goes full bright again when the leads are separated after 

this test, check for polarity reversal on the 0-10V leads.

daylight dimming is disabled in error
AND/OR
occupancy detection scene level set too high

•  Using the programming remote (ISHH-01) ensure the relay can be turned 

ON/OFF and the light level can be raised and lowered.

•  If the load turns ON and responds to the raise/lower commands, follow 

the steps in this document to ensure that daylight dimming is enabled 

and then set the occupancy detection scene level.

Содержание SVPD Series

Страница 1: ...ettings 3 Making Adjustments to Default Scene Levels 4 Step 1 Disable daylighting dimming optional 4 Step 2 Set scene levels 4 Making Adjustments to Other Settings 5 Set sensor time out value 5 Set sensitivity level 5 Enable disable daylight switching 5 Issuing manual commands 5 Troubleshooting guide 5 7 This document applies to fixture with factory installed SVPD1 SVPD2 SVPD3 integrated sensors ...

Страница 2: ...ene level 4 individual fixture Set all fixtures in the space to the desired ON OFF configuration and desired light level then save at each fixture 1 39 2 12 set occupancy time out any time individual fixture 3 50 set occupancy sensitivity any time individual fixture enable disable daylight switching any time individual fixture Sensor Video Integrated sensor and remote overview The SVPD integrated ...

Страница 3: ...on Scene Yes Adjust to any desired light level Unoccupied scene level The light level that the fixture will go to when the space remains unoccupied for the full amount of the programmed occupancy time out period OFF Yes Adjust to any desired light level Occupancy time out The period of time that the lighting will remain at the current level after the space becomes unoccupied 20 min Yes Adjust to 5...

Страница 4: ...l c Set the energy saver scene level optional The occupancy detection scene levels unoccupied scene level and energy saver scene levels are all set using the same procedure with the exception of the button being pressed to save the scene Before you begin Make scene level adjustments at night or use shading with only electric light present in the space This is critical to operation of daylight dimm...

Страница 5: ...nual commands The ISHH 01 programming remote and the ISHH 02 personal remote can issue temporary scene and raise and lower commands Manual commands will remain in effect until the occupancy time out period expires 1 Stand directly below the fixture and point the remote at the integrated sensor 2 Press the scene button ES MIN 50 Occ 75 MAX UnOcc or use the raise and lower control to adjust lighting...

Страница 6: ...C is present between the purple and gray disconnected driver leads If the lighting does go full bright when disconnected from the control module check for polarity reversal on the 0 10V leads daylight dimming is enabled where not appropriate AND OR occupancy detection scene level set too low Using the programming remote ISHH 01 ensure the relay can be turned ON OFF and the light level can be raise...

Страница 7: ...eas determine which fixtures should dim with daylighting If there are fixtures that should not daylight dim follow the steps in this document to disable daylight dimming and set the occupancy detection scene level If the fixtures should dim with daylighting they may need recalibration Follow the steps in this document to set the occupancy detection scene level If the response still does not seem a...

Отзывы: