manualshive.com logo in svg
background image

3

 

 

SVPD Programming Guide

www.eaton.com/lightingsystems

Features and Default Settings

This programming guide discusses how to modify the basic out-of-the-box behavior of the SVPD series sensor (SVPD1, SVPD2, SVPD3). The 

SVPD series integrated sensor allows for quick and easy control of individual luminaires. Out-of-the box, the SVPD integrated sensor will:

•  Turn ON lighting to 100% based on occupancy (daylight adjustment may reduce light level).
•  Reduce lighting during daylight hours based on the availability of natural daylight.
•  Turn off lighting automatically when no occupancy is detected for a period of 20 minutes.

Feature

Description

Default

User Programmable Settings

Occupancy detection 

scene level

The light level the fixture will go to when 

occupancy is detected. If daylight dimming is 

enabled, when the fixture is in this scene at night 

the integrated sensor will “capture” the light 

level. The fixture will use this “captured” level 

as a target to dim the electric lighting during the 

daytime hours.

Auto-ON to 100%

1

•  Yes. Adjust to any desired light 

level. 
•  Adjust to modify daylight dimming 

or daylight switching target light 

level

2

.

Occupancy energy saver 

scene level

The light level that the fixture will reduce to if 

the space remains unoccupied for half of the 

occupancy time-out period.

100% - Occupancy Detection Scene

Yes. Adjust to any desired light level.

Unoccupied scene level

The light level that the fixture will go to when the 

space remains unoccupied for the full amount of 

the programmed occupancy time-out period.

OFF

Yes. Adjust to any desired light level.

Occupancy time-out

The period of time that the lighting will remain 

at the current level after the space becomes 

unoccupied.

20 min.

Yes. Adjust to 5, 10, 15, or 20 

minutes.

Occupancy sensitivity

Adjusts the motion activity coverage area. 

Sensors that pick up motion activity beyond the 

desired area may be set to “LO” to reduce false 

triggering.

High

Yes. Adjust to high or low.

Daylight dimming

Automatically dims the electric lighting in 

response to natural daylight in the space.

Enabled

Yes. Disable or enable daylight 

dimming.

Daylight switching

3

Automatically turns OFF the fixture through an 

internal relay when daylight contribution exceeds 

150% of the maximum nighttime light level 

output (based on occupancy detection scene light 

level captured at night). Lighting will remain OFF 

for 30 minutes and then re-evaluate based on the 

light level and occupied state.

Disabled

Yes. Disable or enable daylight 

switching.

1

 If daylight dimming is enabled, the fixture may dim below this level based on available daylight.  

2

 If daylight dimming or daylight switching are enabled, adjustments to the occupancy detection scene will raise or lower the target level for 

the daylight dimming or daylight switching.  

3

 Daylight switching is recommended only for outdoor applications.

Содержание SVPD Series

Страница 1: ...ettings 3 Making Adjustments to Default Scene Levels 4 Step 1 Disable daylighting dimming optional 4 Step 2 Set scene levels 4 Making Adjustments to Other Settings 5 Set sensor time out value 5 Set sensitivity level 5 Enable disable daylight switching 5 Issuing manual commands 5 Troubleshooting guide 5 7 This document applies to fixture with factory installed SVPD1 SVPD2 SVPD3 integrated sensors ...

Страница 2: ...ene level 4 individual fixture Set all fixtures in the space to the desired ON OFF configuration and desired light level then save at each fixture 1 39 2 12 set occupancy time out any time individual fixture 3 50 set occupancy sensitivity any time individual fixture enable disable daylight switching any time individual fixture Sensor Video Integrated sensor and remote overview The SVPD integrated ...

Страница 3: ...on Scene Yes Adjust to any desired light level Unoccupied scene level The light level that the fixture will go to when the space remains unoccupied for the full amount of the programmed occupancy time out period OFF Yes Adjust to any desired light level Occupancy time out The period of time that the lighting will remain at the current level after the space becomes unoccupied 20 min Yes Adjust to 5...

Страница 4: ...l c Set the energy saver scene level optional The occupancy detection scene levels unoccupied scene level and energy saver scene levels are all set using the same procedure with the exception of the button being pressed to save the scene Before you begin Make scene level adjustments at night or use shading with only electric light present in the space This is critical to operation of daylight dimm...

Страница 5: ...nual commands The ISHH 01 programming remote and the ISHH 02 personal remote can issue temporary scene and raise and lower commands Manual commands will remain in effect until the occupancy time out period expires 1 Stand directly below the fixture and point the remote at the integrated sensor 2 Press the scene button ES MIN 50 Occ 75 MAX UnOcc or use the raise and lower control to adjust lighting...

Страница 6: ...C is present between the purple and gray disconnected driver leads If the lighting does go full bright when disconnected from the control module check for polarity reversal on the 0 10V leads daylight dimming is enabled where not appropriate AND OR occupancy detection scene level set too low Using the programming remote ISHH 01 ensure the relay can be turned ON OFF and the light level can be raise...

Страница 7: ...eas determine which fixtures should dim with daylighting If there are fixtures that should not daylight dim follow the steps in this document to disable daylight dimming and set the occupancy detection scene level If the fixtures should dim with daylighting they may need recalibration Follow the steps in this document to set the occupancy detection scene level If the response still does not seem a...

Отзывы: