SVPD Programming Guide

www.eaton.com/lightingsystems

Quick Reference Guide

This guide is provided as a quick reference. Please review this document in its entirety prior to adjusting settings.

ISHH-01

ISHH-02

Function

Order

Adjustment

Time

Adjustment

Recommendation

Special Instructions

Save Setting Command

Sensor Video 

Time

enable/

disable 

daylight 

dimming

1

individual fixture

For fixtures located 

in non-daylight 

zones, disable 

daylight dimming

00:58

set 

occupancy 

detection 

scene level

2

all fixtures in space

Set all fixtures in 

the space to the 

desired ON/OFF 

configuration and 

desired light level 

then save at each 

fixture

1:39
2:12

set 

unoccupied 

scene level

3

all fixtures in space

Set all fixtures in 

the space to the 

desired ON/OFF 

configuration and 

desired light level 

then save at each 

fixture

1:39
2:12

set 

occupancy 

energy saver 

scene level

4

individual fixture

Set all fixtures in 

the space to the 

desired ON/OFF 

configuration and 

desired light level 

then save at each 

fixture

1:39
2:12

set 

occupancy 

time-out

any 

time

individual fixture

-

3:50

set 

occupancy 

sensitivity

any 

time

individual fixture

-

enable/

disable 

daylight 

switching

any 

time

individual fixture

-

Sensor Video

Integrated sensor and  

remote overview

The SVPD integrated sensor is installed in the selected fixture at the 

factory. Once power is applied, the sensor will begin operation after 

a 1 minute power up period. Motion activity will cause the sensor’s 

red LED to flash.  The sensor’s red LED may also flash differently 

during programming. 

The SVPD integrated sensor’s default behavior is adjusted using the 

ISHH-01 programming remote. The ISHH-02 personal remote is also 

available to allow for scene recall and temporary light level changes.

= Perform this adjustment  

   any time of day or night

= Perform this adjustment  

   at night or when no 

   daylight is present

= Do not move for 10 seconds 

   prior to performing the  

   "SET" command

Содержание SVPD Series

Страница 1: ...ettings 3 Making Adjustments to Default Scene Levels 4 Step 1 Disable daylighting dimming optional 4 Step 2 Set scene levels 4 Making Adjustments to Other Settings 5 Set sensor time out value 5 Set sensitivity level 5 Enable disable daylight switching 5 Issuing manual commands 5 Troubleshooting guide 5 7 This document applies to fixture with factory installed SVPD1 SVPD2 SVPD3 integrated sensors ...

Страница 2: ...ene level 4 individual fixture Set all fixtures in the space to the desired ON OFF configuration and desired light level then save at each fixture 1 39 2 12 set occupancy time out any time individual fixture 3 50 set occupancy sensitivity any time individual fixture enable disable daylight switching any time individual fixture Sensor Video Integrated sensor and remote overview The SVPD integrated ...

Страница 3: ...on Scene Yes Adjust to any desired light level Unoccupied scene level The light level that the fixture will go to when the space remains unoccupied for the full amount of the programmed occupancy time out period OFF Yes Adjust to any desired light level Occupancy time out The period of time that the lighting will remain at the current level after the space becomes unoccupied 20 min Yes Adjust to 5...

Страница 4: ...l c Set the energy saver scene level optional The occupancy detection scene levels unoccupied scene level and energy saver scene levels are all set using the same procedure with the exception of the button being pressed to save the scene Before you begin Make scene level adjustments at night or use shading with only electric light present in the space This is critical to operation of daylight dimm...

Страница 5: ...nual commands The ISHH 01 programming remote and the ISHH 02 personal remote can issue temporary scene and raise and lower commands Manual commands will remain in effect until the occupancy time out period expires 1 Stand directly below the fixture and point the remote at the integrated sensor 2 Press the scene button ES MIN 50 Occ 75 MAX UnOcc or use the raise and lower control to adjust lighting...

Страница 6: ...C is present between the purple and gray disconnected driver leads If the lighting does go full bright when disconnected from the control module check for polarity reversal on the 0 10V leads daylight dimming is enabled where not appropriate AND OR occupancy detection scene level set too low Using the programming remote ISHH 01 ensure the relay can be turned ON OFF and the light level can be raise...

Страница 7: ...eas determine which fixtures should dim with daylighting If there are fixtures that should not daylight dim follow the steps in this document to disable daylight dimming and set the occupancy detection scene level If the fixtures should dim with daylighting they may need recalibration Follow the steps in this document to set the occupancy detection scene level If the response still does not seem a...

Отзывы: