CEAG Remote Display for Central Power Supply Systems   

40071860348   October 2019   www.ceag.de

4.2.6 Features

Use joy-stick to access “Features” menu where you can 

enable or disable additional system features like:  
1. BBM (Battery Block Monitoring)
2. Remote Panel

BBM (Battery Block Monitoring)

Battery Block Monitoring function is always enabled. 
Sealed batteries in accordance with EN 60896-2 provide 

the energy to operate the emergency lighting in the event 

of a power failure in the general 230V mains supply. Dur-

ing normal operations SelvGuard device monitors the state 

of the batteries and if required it recharges them gently.
On the controller board, there is built in capability for bat-

tery monitoring which measures and displays individual 

battery voltage in addition to current and battery compart-

ment temperature. With this, you can measure individual 

battery voltage so you can timely detect a fault in the bat-

tery string. This allows you to reduce maintenance time 

and cost.
The battery is connected to the controller board via a bat-

tery disconnector mounted on the DIN rail (6mm² -10mm²). 

The battery leads are each led through an ISO gland (PG 

gland) into the battery compartment.
SelvGuard was developed and manufactured in conformity 

with the following EC guidelines:
• Low Voltage Directive 2006/95/EC
• Guideline 2004/108/EC on electromagnetic compatibility
Details on the national (DIN), European (EN) and inter-

national (IEC) norms that must be complied with can be 

found in the CE conformity declaration for the device.

Main menu

Monitor
System info
TestTest
Faults and Events
Config Parameters

Features

Display settings

Features

BBM

Remote Panel

Back

OK

Cancel

Back

OK

Cancel

Back

OK

Cancel

Back

OK

Cancel

BBM

Enable

Faults and Events

Active Fault
Fault Log
Event Log

BBM Log

BBM Log (1/10)

49.7 V  

  -0.9 A

B1 12.2 V    B2 12.4 V
B3 12.3 V    B4 12.8 V
+32°C   

  10:25:02

4.2.6 Features

Содержание SG48-RC-LCD-30

Страница 1: ...r Central Power Supply Systems Mounting and Operating Instructions Remote Display for Central Power Supply Systems Target group part 1 Qualified electrician acc to EN 50110 1 Target group part 2 Electrical instucted persons ...

Страница 2: ...7 4 1 1 Monitor 7 4 1 2 System info 7 4 1 3 Language 7 4 1 4 Login 8 4 2 Admin main menu 10 4 2 1 Display settings 10 4 2 2 Block and Reset Alarm 11 4 2 3 Test 11 4 2 4 Faults and Events 11 4 2 5 Config Parameters 13 4 2 6 Features 19 4 2 7 Manage Account 20 4 2 8 Logout 20 5 Servicing Maintenance 20 6 Disposal Recycling 20 Notes 21 General Safety instructions devices 22 Contents 1 General Informa...

Страница 3: ... be disabled at any time reconnecting a remote display to the system will not automatically enable functionality Functionality shall be enabled via Features menu 4 6 2 Features Remote display provides a mirror display of SelvGuard local display Only the display logged in as Admin will operate at a time Normal operation will resume after logout or automati cally 5 minutes after back light time off ...

Страница 4: ... screws on the wall or desk If using concealed cable please run cable through the mounting base first Remote display 55 wall side entry wall back entry desk wall side entry wall back entry desk Remote display 30 LEDs LEDs LEDs LEDs User viewing side User viewing side User viewing side User viewing side Navigation switch Navigation switch Navigation switch Navigation switch LEDs LEDs User viewing s...

Страница 5: ...ll be mounted with the grommet top side like below figure Figure 6 wall mounting installation left desk mounting installation right Figure 5 installing concealed cable left or cable coming below right Connect the cable to the Remote display terminal Rotate the Remote display to almost 45 push it against the mounting base and turn it straight like below figures Figure 8 fixing main display module o...

Страница 6: ...cel Ok button when available on the screen Press enter selected menu select deselect any row for editing escape editing When cursor is on Back Cancel or Ok button press joy stick for action LCD actions buttons Goes to previous menu Save go to previous menu Goes to previous menu without saving 5 way joystick Back OK Cancel Back OK Cancel Back OK Cancel Buzzer Status LEDs LEDs status Status LED Oper...

Страница 7: ...oad Power PSU1 Current Only Admin can view PSU2 Current Only Admin can view and visible only for 900W and 1200W systems PSU Voltage Only Admin can view Monitor Batt Vtg 52 00 V Charge Crt 00 20 A Discharge Crt 00 00 A 4 1 3 Language Use joy stick to select language menu where you can select change desired language Available options are English French and German Main menu Monitor System Info Langua...

Страница 8: ...ow instructions described in chapter 4 2 5 Config Parameters Change password Admin Login and its Main Menu In main menu screen press on Login option It will switch in to login screen Select Admin After successful login Main Menu will show additional sub menus like below User Login and its Main Menu If User is activated you can login as User from Login menu To recover User password enter Recover Pa...

Страница 9: ... OK Cancel Back OK Cancel Back OK Cancel Back OK Cancel Back OK Cancel Back OK Cancel Recover Password To recover password firstly call email your Eaton service cen ter and provide your details together with the controller Serial Number You ll find serial number on the System Info page un der SN after you send this number to your service center you will receive a 6 digit password which you will ne...

Страница 10: ...joy stick to select adjust and store buzzer functional ity You can select out of four options Mute Low Medium and High By default buzzer is muted Enter Buzzer tab to activate buzzer by selecting Low Medium High sound level In configuration mode the buzzer will sound for 2 seconds so you can acknowledge the sound level In case of an alarm or fault the buzzer will sound for 5 seconds continuously an...

Страница 11: ...se joy stick to access Test menu options Functional Test FT Duration Test DT and Cancel FT DT Use joy stick To start FT functional test or DT duration test A pop up message will appear FT in progress or DT in progress and then switch to Home Screen showing FT Ongoing After the function test has finished a message will appear with one of the states FT Passed FT Failed or FT Ab orted All messages wi...

Страница 12: ...ther assistance 9 Batt High Charging If the battery charging current is greater than expected battery charging current then Battery High charging current fault is shown The load and the battery switch will be opened in this scenario 10 Batt Reverse If battery is connected in reverse Batt Reverse Fault is shown The 5 way dis play switch will be locked in this scenario 11 Overtemperature or Under te...

Страница 13: ...ing evacuation Default value is 1 minute and it can be adjusted in minutes from 1 to 99 min If batteries are replaced with different battery than the original factory parameters should change accordingly Please do so under Eaton trained personel supervison If changes have been made a confirmation message will appear before leaving Battery menu and making any changes notification means parameter sa...

Страница 14: ...ional Input menu where you can select Z Inputs functionality Together with Z Inputs functionality you need to select how this function ality will be triggered Level trigger Edge trigger Available functions Optional input functions Edge Trigger Level Trigger 1 No Function Default 2 Output1 O1 3 Output2 O2 4 FT start 5 DT start 6 Cancel FT DT 7 Manual reset 8 Deep Discharge Ack 9 Ventilator Monitor ...

Страница 15: ...Input 1 and Secure Input 2 can t have same func tion simultaneously Upon activation of Rest Inhibit home screen will be updated as Mains Inhibit like in screen to the right FT DT Settings Use joy stick to access FT DT Settings menu where you can change the Functional Test and Duration Test settings To save configuration follow same steps as in previous section If FT DT date is due and prerequisite...

Страница 16: ...k the selected functios In right screen for example Relay 1 is used to signalize Mains Faults Charge Fault or Circuit Fault CKT Fault To save configuration follow same steps as in previous section Date and Time Use joy stick to access Date and Time menu where you can edit time and date settings Move cursor over the field you want to chanve and when cursor starts blinking use joy stick up and down ...

Страница 17: ...or validation or select cancel if you want to skip To see defaults parameters list check SelvGuard instal lation manual chapter 6 2 5 Config Parameters Factory Defaults After 2 3 seconds it will switch to Home Screen Pop up message Back OK Cancel Back OK Cancel Extended Emergency In this section Admin can adjust Delay On Mains Return features Manual Automatic and Duration time Delay On Mains Retur...

Страница 18: ...ge Password Use joy stick to access Change Password where you can set a new password for Admin or User Housekeeper Use joy stick up and down to go on Admin or User and press joy stick to select Admin can also set change the password for the User housekeeper account When exit Config parameters screen it will show Config Saving message If Admin is deactivated on every power on or when switch to Home...

Страница 19: ...an measure individual battery voltage so you can timely detect a fault in the bat tery string This allows you to reduce maintenance time and cost The battery is connected to the controller board via a bat tery disconnector mounted on the DIN rail 6mm 10mm The battery leads are each led through an ISO gland PG gland into the battery compartment SelvGuard was developed and manufactured in conformity...

Страница 20: ...le Enable User Enable Disable Enable Faults and Events Config Parameters Features System Info Language Manage Account Logout Enable Disable Enable Disable 4 2 8 Logout After all changes have been made you can log out using this menu from either Admin or User account If no activity Admin or User account will be logged out 5 minutes after the back light time off E g Admin User Logout time Backlight ...

Страница 21: ...21 CEAG Remote Display for Central Power Supply Systems 40071860348 October 2019 www ceag de Notes Notes ...

Страница 22: ...h General safety instructions The devices are not suitable for private use An installation must be performed by qualified electricians taking into account the national safety and accident prevention regulations The devices must be used in accordance with their intended use in a proper and undamaged condition Remove all foreign objects from the devices before their first use When working with the d...

Страница 23: ...limentarea cu curent asigurați le împotriva repornirii și verificați ca să nu fie sub tensiune Cele de mai sus se referă la alimentarea de la rețea alimentarea de rezervă tensiunea de reglare și curenții de scurgere Nu întrerupeți circuitele sub sarcină Fiți atenți la obiecte care pot cădea în timpul transportului Utilizați numai piese de schimb originale Pусский Общие инструкции по безопасности У...

Страница 24: ...ices critical industries around the globe count on Eaton We power businesses with reliable efficient and safe electrical power management solutions Combined with our personal service support and bold thinking we are answering tomorrow s needs today Follow the charge with Eaton Visit eaton eu You will find your contact partner at www ceag de Eaton is dedicated to ensuring that reliable efficient an...

Отзывы: