Universal Bus Adapter 

Proceed with the following 3 steps:

Step 1: 

Bolt a universal bus adapter

to the vertically positioned mounting

holes of a primary terminal pad for a

horizontal bus connection or to the

horizontally positioned mounting

holes for a vertical bus connection as

shown using the hardware provided.

Torque the bolted connection to 120

in-lbs (13.6 N-m) using a torque

wrench. 

Step 2: 

Complete all six adapter

connections (eight for 4-pole) in a

similar fashion.  The line and load

adapters can be mounted in opposite

directions as shown. 

Step 3: 

Reverse the procedure just

described to remove the adapters.

Cable Adapter 

Proceed with the following 4 steps:

Step 1: 

A cable adapter can be bolt-

ed directly to the straight bus

adapter using the hardware provided

as shown.  Torque the bolted con-

nection to 240 in-lbs (27 N-m) using

a torque wrench. 

.  

Step 2: 

Complete all six cable

adapter connections (eight for 4-

pole) in a similar fashion.  Make cer-

tain that the adapters are mounted

pointing in the proper direction as

shown. 

Step 3: 

Reverse the procedure just

described to remove the adapters.

Step 4: 

When making the actual

cable connections, properly torque 

Step 1

Step 2

Step 1

Step 2