Enterprise Power Solutions Installation and Operation Guide
20
Copyright © 2008 Eaton Corporation. All Rights Reserved.
IPN 997-00012-56C September 2008
"
Protective earthing conductor to protective earth bar in building.
Step 4 - Set Output to Floating if required (otherwise go to next Step)
The EPS2/EPS5 can be configured with either the output positive
connected to ground (standard) or with a floating output (optional).
1
Check if the equipment to be powered requires a dc supply with
output positive connected to ground or with a floating output.
2
If the equipment to be powered requires that the dc output of the
EPS2/EPS5 is "floating" (not bonded to ground), then remove the
output-ground screw. No further action is required.
"
Output-ground screw removed for
"floating" output.