Maintenance
Copyright © 2008 Eaton Corporation. All Rights Reserved.
IPN 997-00012-56C September 2008
57
Step 4 - Download the configuration file
1
Connect to the system controller with
DCTools
.
2
If a copy of the old configuration file, or a master configuration file is
available, then use
DCTools
to restore (download) it to the new system
controller.
See Backup and Restore on page
.
If you receive an error message about the MIB file version, please contact
your Eaton dc product supplier for advice.
3
If a copy of the old configuration file, or a master configuration file is not
available, then use the keypad or
DCTools/Web
to change the configuration
settings to the correct values (provided the system controller is set for the
correct nominal system voltage).
Step 5 - Check the system controller operation
1
Map the I/O board (SC200 only):
•
In DCTools/Web go to:
I/O Board
>
I/O Board to Serial Number Mapping
.
•
Copy the I/O board serial number(s) from the
RXP Bus Slaves
table to
the
I/O Board to Serial Number Mapping
table to map an
IOB Number
to
each I/O board (overwrite an existing serial number if required).
2
Check that the system controller has registered all rectifiers.
3
Check all control processes, alarms and current measurement(s).
4
Check the power system identification parameters and communications
settings.
5
Change the configuration file as required to ensure that the system
controller operates as intended.
6
Check the system controller time (SC200 only). See details in system
controller handbook.