Preparation
Copyright © 2008 Eaton Corporation. All Rights Reserved.
IPN 997-00012-56C September 2008
11
Servicing
•
The dc power system contains hazardous voltages and hazardous energy levels. Do not attempt
to disassemble or service the unit if you are not qualified.
EMC Compliance
•
This Powerware product ("the equipment") has been tested and found to comply with the limits
for a Class B digital device, pursuant to part 15 of the Federal Communications Commission
(FCC) Rules. These limits are designed to provide reasonable protection against harmful
interference in a residential installation.
•
The equipment generates, uses, and can radiate radio frequency energy and, if not installed and
used in accordance with the instructions in this installation guide, may cause harmful
interference to radio communications. However, there is no guarantee that the interference will
not occur in a particular installation.
•
If the equipment does cause harmful interference to radio or television reception, which can be
determined by turning the equipment off and on, the user is encouraged to try to correct the
interference by one or more of the following measures:
•
Reorient or relocate the receiving antenna.
•
Increase the separation between the equipment and receiver.
•
Connect the equipment into an outlet on a circuit different from that to which the receiver is
connected.
•
Consult the dealer or an experienced radio/TV technician for help.
•
Changes or modifications to the equipment not approved by Eaton Corporation could void the
FCC authority to operate the equipment.
Telecom Ground and dc Supply Bond to Chassis
•
CAUTION: This equipment has a connection between the earthed conductor of the dc supply
circuit and the earthing conductor.
Cet appareil comporte une connexion entre le conducteur relié à la terre du circuit d'alimentation c.c. et
son conducteur de terre.
•
All of the following installation conditions must be met:
•
This equipment shall be connected directly to the dc supply system earthing electrode
conductor or to a bonding jumper from an earthing terminal bar or bus to which the dc
supply system earthing electrode conductor is connected.
•
This equipment shall be located in the same immediate area (such as adjacent cabinets) as
any other equipment that has a connection between the earthed conductor of the same dc
supply circuit and the earthing conductor, and also the point of earthing of the dc system.
The dc system shall not be earthed elsewhere.
•
The dc supply source shall be located within the same premises as this equipment.
•
Switching or disconnecting devices shall not be in the earthed circuit conductor between the
dc source and the point of the connection of the earthing electrode conductor.
•
Ce matériel doit être raccordé directement au conducteur de la prise de terre du circuit d'alimentation c.c.
ou à une tresse de mise à la masse reliée à une barre omnibus de terre laquelle est raccordée à l'électrode de
terre du circuit d'alimentation c.c. Les appareils dont les conducteurs de terre respectifs sont raccordés au
conducteur de terre du même circuit d'alimentation c.c. doivent être installés à proximité les uns des
autres (p.ex., dans des armoires adjacentes) et à proximité de la prise de terre du circuit d'alimentation c.c.
Le circuit d'alimentation c.c. ne doit comporter aucune autre prise de terre. La source d'alimentation du
circuit c.c. doit être située dans la même pièce que le matériel. Il ne doit y avoir aucun dispositif de
commutation ou de sectionnement entre le point de raccordement au conducteur de la source
d'alimentation c.c. et le point de raccordement à la prise de terre.