Rating Plug
All Magnum SB circuit breaker trip units use a fixed type
rating plug . The current rating of the rating plug must match
the current rating of the integrally mounted current sensors
(
Figures 6 and 34 and Table 6
) . The rating plug performs
several functions:
1 It tells the trip unit what the rating is of the current sensors .
A label on the front of the rating plug clearly indicates that
the rating plug and sensors must have the same rating .
2 It determines the maximum instantaneous setting which is
a function of the current sensor rating .
3 The National Electrical Code (NEC) requires that the
maximum ground fault pickup value not exceed 1200
amperes . A properly matched rating plug accomplishes this
requirement for higher ampere sensors by incorporating
circuitry to identify that level by sensor rating .
If the rating plug is removed from the trip unit, the circuit
breaker will trip if it is carrying current . Make certain the rating
plug is secured in position with its retaining screw . Do not
torque the retaining screw beyond 15 In-Oz .
Refer to
Table 6
for a tabulation of the available rating plugs .
Current Sensors
Three toroidally wound current sensors are installed at the
rear of the circuit breaker on the lower terminals (
Figure 36
) .
The sensors produce an output current proportional to the load
current . Under preselected conditions of current magnitude
and time, the sensors furnish the trip unit with a signal and the
energy required to trip the circuit breaker .
Neutral current sensors are available for customer installation .
The additional sensor is not supplied with the circuit breaker
and must be ordered separately . They are wired to the trip unit
through the secondary contacts of the circuit breaker .
Refer to
Table 6
for a tabulation of the available current sensor
ratings .
Test
Receptacle
Rating Plug
Pop Out Trip
Flag
Auxiliary Power
Module Port
Figure 34. Digitrip RMS 1150 Programmable Trip Unit Installed in
Magnum SB Circuit Breaker
Figure 35. Hand Held Tester