Instructions for Installation, Operation and
Maintenance of Magnum SB Insulated Case
Low Voltage Power Circuit Breakers
EATON CORPORATION
www.eaton.com
Instructional Leaflet
IB2C12063H03
Effective March 2012
Section 5: Fixed Circuit Breaker
General
Section 3 discussed topics and features common to all
Magnum SB circuit breakers, no matter what the mounting
configuration or type . In this section, features unique to
the fixed configuration not covered elsewhere are covered .
Drawings and dimensions associated with all fixed circuit
breakers and any appropriate primary bus connections can
be found in a separate document entitled Engineering Data
TD01301004E . The installation of a fixed circuit breaker was
discussed in Section 2 . If necessary, review that information,
since it will not be repeated here .
WARNING
FAILURE TO COMPLY WITH INSTALLATION OF THE FIXED MOUNTED
SBSE ARC HOOD ASSEMBLY COULD RESULT IN EQUIPMENT
DAMAGE, BODILY INJURY OR EVEN DEATH.
The SBSE fixed mounted breaker is shipped with a factory
installed arc hood assembly . This assembly is required to be
installed on the top of the breaker prior to the unit being placed
in service .
Fixed Circuit Breaker Dimensions
The standard fixed circuit breaker is supplied with horizontally
mounted primary connections (
Figure 87
) . Optional vertical
primary adaptors are available for different bus configurations .
Refer to Engineering Data TD01301004E for fixed circuit breaker
dimensions, vertical adaptor dimensions and vertical adaptor
assembly details .
Figure 87. Fixed Circuit Breaker with Available Vertical Adaptor
Horizontal
Connection
Optional
Vertical
Adaptor