66
Instructions for Installation, Operation and
Maintenance of Magnum SB Insulated Case
Low Voltage Power Circuit Breakers
EATON CORPORATION
www.eaton.com
Instructional Leaflet
IB2C12063H03
Effective March 2012
Figure 100. Magnum DS Lubrication—Levering-in Mechanism
Figure 101. Magnum DS Lubrication—Levering-in Mechanism
Circuit Breaker Modifications And Changes
The topics discussed here will relate to those actions that can
be taken in the field to change, update, maintain or repair a
Magnum SB circuit breaker . This information does not, however,
include most accessory devices . Their installation is covered by
separate instruction leaflets dedicated to the individual devices .
The tasks described here do not, under ordinary circumstances,
require any assistance beyond the appropriate instructional
material . If further assistance is required, however, contact your
Eaton representative .
Rating Plug Replacement
ote:
N
If a rating plug is not installed in the trip unit, the trip
unit will trip when energized . Also remember that the trip unit’s
rating plug and the circuit breaker’s current sensors must have
matching ratings .
To remove the rating plug from the trip unit, open the small
rating plug door located on the right side of the trip unit (
Figure
102
) . The trip unit’s battery cavity is also located behind this
door . Use a 1/8” wide screwdriver to remove the M4 screw
holding the rating plug in position . Pull the door to release the
rating plug from the trip unit .
Figure 102. Trip Unit Rating Plug Location
To install a new rating plug, insert the rating plug into the cavity
where the other rating plug was removed . Make sure the three
pins on the rating plug are aligned with the sockets in the
cavity . The rating plug should fit with a slight insertion force .
CAUTION
TO PREVENT DAMAGE TO THE RATING PLUG, DO NOT FORCE IT INTO
THE MOUNTING CAVITY.
Use the same 1/8” screwdriver to tighten the M4 screw and
secure the rating plug in the trip unit . The maximum torque on
the mounting screw is 15 in-oz . Close the rating plug door .