Section 7: Troubleshooting
Introduction
Table 16
will help to determine the probable causes of simple
circuit breaker problems and possible corrective actions .
Possible problems associated with the electronic trip unit
are covered in companion publications, IL70C1037H05 and
IL70C1036H06 . If the problem cannot be resolved with the
aid of one or both of these guides, contact the Cutler-Hammer
service center for more in-depth assistance .
Table 16. Circuit Breaker Troubleshooting Guide
Symptom
Probable Cause
Corrective Actions
The circuit breaker trips open
(red fault trip indicator button
is out and/or fault indicator LED
is lighted) when closed on a
load current
Rating plug not installed
and load current through
the breaker
Install rating plug that
corresponds to current sensors
Repeated closing on
transient (in-rush) current
with thermal memory
active
Wait for circuit breaker (and
loads) to cool before re-closing
Use status and fault indicators
to help locate and remove
overload or fault condition
An overload or fault
current condition
Circuit breaker opens
(fault trip indicator button
is not out)
Undervoltage release
operates; voltage too low
or zero
Check and correct the UVR
supply voltage (85-110% rated
voltage)
Check control signal(s) to
shunt trip; correct if necessary
Shunt trip operates
Inspect latch condition and
engagement before closing;
consult Cutler-Hammer service
center
Trip latch is defective
Circuit breaker cannot
be opened remotely, but
can be opened locally
Shunt trip control signal
absent or too low
Check supply voltage exceeds
70% of rated voltage when
signal is applied to shunt trip
Remove front cover; check
voltage supplied to shunt
trip; make sure shunt trip is
seated and retainer snapped
into place. Check for shunt
trip motion; replace shunt
trip if faulty
Shunt trip is faulty or
improperly installed
Make sure electrical pin and
socket connectors are properly
seated in molded plug. Verify
proper wiring
Secondary contact wiring
problem
Circuit breaker cannot
be opened locally
OPEN pushbutton locked
Remove lock
Faulty mechanism or
main contacts welded
Contact Cutler-Hammer
service center
Circuit breaker makes
no attempt to close with
either local (manual) or
remote controls; springs
do not discharge
Closing spring not fully
charged (check SPRING
CHARGED indicator)
Charge spring manually; check
voltage to electrical operator;
replace electrical operator if
faulty
Unplug undervoltage release
from mounting deck and retry
closing operation; if OK, check
voltage supply to undervoltage
release (>85%); replace
undervoltage release if faulty
If equipped with
undervoltage release,
undervoltage release is
not energized or is faulty
Circuit breaker locked in
OPEN position
Check reason for lock
Drawout position
interlock is operating;
levering screw
Make sure that circuit breaker
is at a position that permits
closure; door is open check that
shutter (door) over the levering
screw is fully closed
Circuit breaker
interlocked with another
circuit breaker or device
Check for presence of an
interlocking scheme (cable
interlock or key interlock);
check to see if interlocked
circuit breaker is CLOSED
Circuit breaker cannot be closed
remotely (can be closed locally)
Spring release (closing)
coil supply voltage low or
spring release faulty
Check power supply voltage;
replace spring release if faulty
Secondary contact wiring
problem
Make sure electrical pin and
socket connectors are properly
seated in molded plug. Verify
proper wiring
Spring release closing
coil signal blocked
Clear Digitrip 1150 relay
contact
Circuit breaker cannot be closed
locally (but can be closed
remotely)
Opening and/or closing
pushbuttons locked
Check reason for lock
Circuit breaker does not
recharge electrically but will
recharge manually
Charging motor supply
voltage absent or too low
(<85%)
Check charging motor electrical
circuit voltage (check under
load)
Charging motor faulty
Replace charging motor
assembly
Drawout circuit breaker will not
lever-in
Circuit breaker will not
fully enter cell (cell
rejection code plate)
Circuit breaker ratings do not
correspond to the cassette
requirements
Levering-in screw not
in fully DISCONNECT
position at insertion
Rotate levering-in screw
counterclockwise to
DISCONNECT position, then
insert breaker fully into
cassette
Levering-in screw in
DISCONNECT position
but not pushed in far
enough
Push circuit breaker in as far
it will go, cover should be
flush with front of cassette
side plate
Protective boots covering
stationary disconnects
Remove boots
Shutter jammed or
locked
Clear problem